Storage temperature range of MCCBs and ELCBs
It is from -25 to 55℃ in Trip or OFF position. However, it shall be in an environment without condensation and freezing even in a short time. More Details >>
- No:22426
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
If switching of neutral pole is not needed, it is possible to use 3-pole MCCB for 3-phase 4- wire circuit. Generally, it is recommended to use 4-pole circuit... More Details >>
- No:22385
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Operating characteristics described in our catalog (if there is no "Note" particularly) mean operating time when it starts to carry current from the conditio... More Details >>
- No:22374
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It is a protection method which only trips the related circuit breaker and other fault-free circuit does not trip and continues power supply in the event of... More Details >>
- No:22366
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It is an earth leakage current (Effective value of residual operating current) which definitely trips Earth Leakage Circuit Breaker and Earth Leakage Relay ... More Details >>
- No:22353
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Large electromagnetic force will be generated between conductors/wires due to fault currents. To prevent deformation and breakage of circuit breakers and con... More Details >>
- No:22424
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Change Electronic relay characteristics when it is energized
Only electricians who have enough technical knowledge should change the setting of overcurrent tripping and earth leakage tripping characteristics. Moreover,... More Details >>
- No:22409
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It means that it does not interfere with tripping operation even if a handle is held at "ON" position. (It trips when an overcurrent flows even if a handle i... More Details >>
- No:22378
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The control power supply of the earth leakage detection circuit is taken from the inside of Earth Leakage Circuit Breaker. If used on the secondary side of t... More Details >>
- No:22372
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
The number of trip durability by using SHT and UVT is 10% of the opening/closing number including the number of trips by overcurrent, trip button and test bu... More Details >>
- No:22407
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components