FAQ


FAQAbout Products

- FAQ > Low-voltage Power Distribution Products > Contactors and Motor Starters
FAQ
Keyword Search
Contactors and Motor Starters
FAQ within [ Contactors and Motor Starters ]
-
About Low-voltage Power Distribution Products
The permissible variation range of frequency (short time variation) is ±5%. More Details >>
- No:23371
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The minimum applicable load is 20V, 3mA . Contact reliability is indicatedby fault rate λ60 (Number of fault / Operating cycles per one contact) atthe reliab... More Details >>
- No:23304
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
A thermal load relay is set as full-load current of a motor. However, ifambient temperature is significantly different from 20℃ or the connectingwire is diff... More Details >>
- No:23238
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The withstand voltage of US-N5SS, US-N8SS, US-N70NS and US-N80NStype is 2kV. The withstand voltage of US-N20 to 50 type is 2.5kV. Theapplied points are as fo... More Details >>
- No:23351
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is possible to operate it by using two US-N* type. For the interlock ofboth US-N* type, UA-RE type reversible unit is used. More Details >>
- No:23375
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is 1500V 50/60Hz between a terminal and a case for 1 min. More Details >>
- No:23310
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
US-N* type can be used for AC power supply motor, heater, lighting loadand capacitor load etc. More Details >>
- No:23365
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
We can provide "CAN terminal" products for only US-N20?50(TE) type asspecial product.Type name:US-N20?50(TE)CX More Details >>
- No:23337
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is not possible to change a contact of SD-Q type. More Details >>
- No:23341
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
This is because the delay time becomes shorter since the rebound force ofa spring against the suction force of a magnetic contactor increases if thecontact "... More Details >>
- No:23309
- Release Date:2018/09/12 15:11
- Category: Motor Starters
1-10 of Total 142