FAQ


FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Contactors and Motor Starters
FAQ
Keyword Search
Contactors and Motor Starters
FAQ within [ Contactors and Motor Starters ]
-
About Low-voltage Power Distribution Products
If both of a closing coil and a tripping coil are continued to excite at thesame time, it will result in coil burnout. You need to design a system thatdoes n... More Details >>
- No:23282
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
You can install it as follows.1. Regular installation of the power supply side terminal as the upper partand the load side terminal as the lower side2. Incli... More Details >>
- No:23283
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The fault detection contact of the cooling fan detects the temperature ofthe fin in the solid state contactor and operates when exceeding thespecified value.... More Details >>
- No:23301
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
There are auxiliary contact (UQ-AX2、UQ-AX2KR) units that can apply forQ11 frame and QR11 frame.1. UQ-AX2 can apply for the left side of Q11 and QR11.2. UQ-AX... More Details >>
- No:23302
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
For US-N5/8SS(TE) and US-N70/80NS(TE), the rated impulse withstandvoltage is 4kV. For US-N20 to 50(TE) and US-NH70/NH80NS(TE), the ratedimpulse withstand vol... More Details >>
- No:23322
- Release Date:2018/09/12 15:11
- Update:2018/09/26 09:22
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
When carrying the rated current at ambient temperature of 40℃ (whencarrying the rated heater load), the maximum temparature of cooling finis approximately 100℃. More Details >>
- No:23358
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
US-N* type is controlled by DC power supply (12 to 24 VDC). However,UA-DR1/UA-SH1 driving-unit of option unit make it possible to control byAC power supply (... More Details >>
- No:23359
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
In our 3-contactor type star-delta starter (EYD), in order to eliminate thebreaking duty of the star contactor (MCS), the main contactor (MCM)break the star-... More Details >>
- No:23239
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is utilization category specified in IEC 60947-4-1. AC-3 category is usedfor starting a motor or stopping during operation etc. More Details >>
- No:23241
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
RC stands for "Rated current" and the thermal load relay is usedaccording to the rated current (Full load current) of a motor. More Details >>
- No:23254
- Release Date:2018/09/12 15:11
- Category: Motor Starters
111-120 of Total 142