FAQ


FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Contactors and Motor Starters
FAQ
Keyword Search
Contactors and Motor Starters
FAQ within [ Contactors and Motor Starters ]
-
About Low-voltage Power Distribution Products
It is a film capacitor, not electrolytic capacitor. More Details >>
- No:23316
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
Since a triac element in UT-SY21 type and UN-SY11/21/31 canopen/close, surge voltage does not occur. Therefore, a coil surgesuppressor is not needed for them. More Details >>
- No:23300
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
These two different colors of the knob identify 2-element type and 3-element type of a thermal load relay. Gray: TH-* (Heater 2-element type)Orange: TH-*KP t... More Details >>
- No:23273
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The Earth Leakaga Circuit Breaker does not work since leakage current ofSSC is the current flowing from the main circuit element to the load sidewhen opening. More Details >>
- No:23338
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The minimum applicable load is as follows. Contact reliability is indicatedby fault rate λ60 (Number of fault / Operating cycles per one contact) atthe relia... More Details >>
- No:23320
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The rated impulse withstand voltage of US-H* type is 6KV. This meets therequired impulse characteristic for power distribution equipment specifiedin IEC stan... More Details >>
- No:23329
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is IP20. More Details >>
- No:23327
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
You need to connect the two terminal of No.15, 16 or 18 terminal to theload side of the contactor. (The remaining terminal is unnecessary toconnect.) More Details >>
- No:23307
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The minimum applicable load is 20V, 3mA . Contact reliability is indicatedby fault rate λ60 (Number of fault / Operating cycles per one contact) atthe reliab... More Details >>
- No:23304
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
At ambient temperature 40℃, the rated voltage (frequency) is applied to acontrol coil, and after temperature rise and saturation, it can operatewithout any t... More Details >>
- No:23278
- Release Date:2018/09/12 15:11
- Category: Motor Starters
11-20 of Total 142