FAQ
FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Contactors and Motor Starters
FAQ
Keyword Search
Contactors and Motor Starters
FAQ within [ Contactors and Motor Starters ]
-
About Low-voltage Power Distribution Products
We can not produce it. More Details >>
- No:23332
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
This is because the delay time becomes shorter since the rebound force ofa spring against the suction force of a magnetic contactor increases if thecontact "... More Details >>
- No:23309
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The minimum applicable load is 20V, 3mA . Contact reliability is indicatedby fault rate λ60 (Number of fault / Operating cycles per one contact) atthe reliab... More Details >>
- No:23304
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
Since the leakage currents exist in a solid state contactor such as US-N/K/H type even when it is "OFF" state, it can not be used for insulatingload equipmen... More Details >>
- No:23288
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
You can make sure with a display window beside the adjustment knob ofthe thermal load relay. If green is displayed in the display window, it isreset state, a... More Details >>
- No:23251
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is utilization category specified in IEC 60947-4-1. AC-1 category is usedfor heater or resistive load etc. More Details >>
- No:23248
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
A thermal load relay is set as full-load current of a motor. However, ifambient temperature is significantly different from 20℃ or the connectingwire is diff... More Details >>
- No:23238
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is the maximum applicable load capacity at rated operational voltage. More Details >>
- No:23236
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
Bearing lifetime of cooling fan is 10,000 to 35,000 hours. However, thelifetime of the cooling fan will be reduced depending on the ambienttemperature rise, ... More Details >>
- No:23364
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
When carrying the rated current at ambient temperature of 40℃, themaximum temparature of cooling fin is approximately 90℃. More Details >>
- No:23360
- Release Date:2018/09/12 15:12
- Category: Motor Starters
31-40 of Total 142