About Low-voltage Power Distribution Products
Since the permanent magnet is used for the electromagnet part of SD-Qtype, it is necessary to match its polarity with the polarity of the controlcoil. More Details >>
- No:23324
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The minimum applicable load is 20V, 3mA . Contact reliability is indicatedby fault rate λ60 (Number of fault / Operating cycles per one contact) atthe reliab... More Details >>
- No:23304
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The functions of 2 and 3 element type are almost same, but since theneutral pole (3/L2, 4/T2) of 3-pole 2-element type is connected inside, itis not possible... More Details >>
- No:23270
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is possible to install them by rotating 90℃ to the right or left from theregular installation except S-N600 and S-N800. It is not possible to rotate180℃ f... More Details >>
- No:23335
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is possible to produce with the coil designation of less than AC 230V andDC 220V. Please add " SA" at the end of the type name. More Details >>
- No:23319
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is the utilization category for opening/closing a heater load ofsemiconductor contactor specified in IEC60947-4-3. Utilization categoryAC-51 applies for "... More Details >>
- No:23318
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is not possible to install it on the floor. If doing that, the weight of themoving part of a magnetic starter itself acts downward against thetripping spr... More Details >>
- No:23312
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
This is because the delay time becomes shorter since the rebound force ofa spring against the suction force of a magnetic contactor increases if thecontact "... More Details >>
- No:23309
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is possible to apply for single-phase circuit. However, it may be lesseffect in single-phase circuit (100 V, etc) since low voltage circuit is tendedto be... More Details >>
- No:23297
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is a current value that can be closed (turning contact "ON") under theconditions specified in the standards. (In IEC, number of tests is 50times) More Details >>
- No:23294
- Release Date:2018/09/12 15:11
- Category: Motor Starters