About Low-voltage Power Distribution Products
It is utilization category specified in IEC 60947-4-1. AC-3 category is usedfor starting a motor or stopping during operation etc. More Details >>
- No:23241
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
In our 3-contactor type star-delta starter (EYD), in order to eliminate thebreaking duty of the star contactor (MCS), the main contactor (MCM)break the star-... More Details >>
- No:23239
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is possible to open/close three-phase load by opening/closing two poleswith three-phase circuit. If US-H opens/closes two poles and theremaining pole is s... More Details >>
- No:23367
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
US-H* is designed for a heater load ,and a driving-circuit and selection ofa main circuit element are also designed to apply for a heater load andwhen applie... More Details >>
- No:23361
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
When carrying the rated current at ambient temperature of 40℃ (whencarrying the rated heater load), the maximum temparature of cooling finis approximately 100℃. More Details >>
- No:23358
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
Time rating is 60sec and the rest time is for 2 hours. More Details >>
- No:23308
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is a circuit that maintains "ON" state even when the "ON" command ofthe control coil disappears by using auxiliary contact "a" of magneticcontactor itself... More Details >>
- No:23295
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
Since US-N/K/H type is a solid state contactor having zero-voltage-triggering method, surge voltage does not occur due to opening/closing amain circuit. More... More Details >>
- No:23291
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
Since the leakage currents exist in a solid state contactor such as US-N/K/H type even when it is "OFF" state, it can not be used for insulatingload equipmen... More Details >>
- No:23288
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is not possible to produce an enclosed magnetic starter with a saturatedreactor. More Details >>