FAQ


FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Contactors and Motor Starters
FAQ
Keyword Search
Contactors and Motor Starters
FAQ within [ Contactors and Motor Starters ]
-
About Low-voltage Power Distribution Products
The Earth Leakaga Circuit Breaker does not work since leakage current ofSSC is the current flowing from the main circuit element to the load sidewhen opening. More Details >>
- No:23338
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
SD-T12 to T32 and SD-N600, N800 type operation coil terminals have polarity. Connect terminal mumber A1 (+) to the positive and A2 (-) to the negative sid... More Details >>
- No:23271
- Release Date:2018/09/12 15:11
- Update:2021/04/09 16:21
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is a current that can be energized for 8 hours without opening/closingthe magnetic contactor and in the state that the temperature rise value ofeach part ... More Details >>
- No:23255
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The withstand voltage of US-H type is 2.5kV. The applied location is asbelow.1. Between a main circuit terminal and a control circuit terminal2. Between all ... More Details >>
- No:23344
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
We can provide "CAN terminal" products for only US-N20?50(TE) type asspecial product.Type name:US-N20?50(TE)CX More Details >>
- No:23337
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is not possible to install it on the floor. If doing that, the weight of themoving part of a magnetic starter itself acts downward against thetripping spr... More Details >>
- No:23312
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
Since a triac element in UT-SY21 type and UN-SY11/21/31 canopen/close, surge voltage does not occur. Therefore, a coil surgesuppressor is not needed for them. More Details >>
- No:23300
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
In the case of DC, since the load current breaking is more difficultcompared to AC, permanent magnet is provided at each main contactpoint and the arc is dri... More Details >>
- No:23289
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is possible to apply if the rated operating current value of a magneticcontator is more than the total rated current of motors. However, athermal load rel... More Details >>
- No:23263
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
We do not provide it. More Details >>
- No:23355
- Release Date:2018/09/12 15:12
- Category: Motor Starters
71-80 of Total 142