      ACB combination Ground fault protection and earth leakage protection It is not possible to combine them at the same time. You need to choose one of them. More Details >> - No:22419
- Release Date:2018/08/31 14:33
 
- 
      
      This contact(SBC) is used to auxiliary switch(AXb) contact. When Drawout type ACB is moved from "test" position to "disconnect" position, AXb contact will b... More Details >> - No:22416
- Release Date:2018/08/31 14:33
 
- 
      ACB How to store drawout handle Set the handle holder to the right side of the drawout frame with the included screw and nut, and store the drawout handle. However, the circuit breaker with... More Details >> - No:22437
- Release Date:2018/08/31 14:33
 
- 
      Release element in neutral (4P breaker) AE-SW 4-poles with WS relay (general protection) has overcurrent protection for neutral-pole. The tripping characteristic is same as phase-pole. Moreover, A... More Details >> - No:22441
- Release Date:2018/08/31 14:33
 
- 
      
      The test position is a position where a main circuit is in the "disconnected" state and only control circuit is in the "connected" state. Control circuit che... More Details >> - No:22405
- Release Date:2018/08/31 14:33
 
- 
      
      (1) and (2) are impossible. More Details >> - No:24818
- Release Date:2019/04/09 15:03
 
- 
      
      Horizontal connection type (standard: AE-SW up to 3200A except 2000-SWA), Vertical connection (VT) type (standard: 2000-SWA,4000-SWA -6300-SW) and Front conn... More Details >> - No:22417
- Release Date:2018/08/31 14:33
 
- 
      
      The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >> - No:22440
- Release Date:2018/08/31 14:33
 
- 
      ACB General use Generator protection use General protection relay (WS) of AE-SW type Air Circuit Breaker has tripping characteristic and function for general use. However, we also provide the replay... More Details >> - No:22414
- Release Date:2018/08/31 14:33
 
- 
      
      It is a standard equipment (automatic reset type) and 30ms of one-pulse is output at overload tripping. Hold-type circuit is necessary since the output time ... More Details >> - No:22428