FAQ within [ Air Circuit Breakers ]

11-20 of Total 23

prev 2 / 3page next
  • ACB trip indication

    Generally, there is no Mechanical Trip indication of continuous output for AE-SW. It is necessary to indicate electrically by using OCR Alarm (AL) output or ... More Details >>

    • No:22432
    • Release Date:2018/08/31 14:33
  • ACB Shorting B contact (SBC)

    This contact(SBC) is used to auxiliary switch(AXb) contact. When Drawout type ACB is moved from "test" position to "disconnect" position, AXb contact will b... More Details >>

    • No:22416
    • Release Date:2018/08/31 14:33
  • ACB add earth leakage protection

    When earth leakage current protection module (ER) is attached, it is possible to protect against earth leakage current. "Trip" or "Alarm signal output" can b... More Details >>

    • No:22420
    • Release Date:2018/08/31 14:33
  • ACB closing time

    The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>

    • No:22440
    • Release Date:2018/08/31 14:33
  • ACB drawout position

    Drawout type circuit breaker can be drawn-out and insert to the cradle without taking out the connecting conductor. As ACB is drawn out, it will be "connect ... More Details >>

    • No:22431
    • Release Date:2018/08/31 14:33
  • ACB combination Ground fault protection and earth leakage protection

    It is not possible to combine them at the same time. You need to choose one of them. More Details >>

    • No:22419
    • Release Date:2018/08/31 14:33
  • ACB DC use

    It is not possible to use standard AE-SW in DC circuit. Special DC use AE-SW is provided if specified. More Details >>

    • No:22446
    • Release Date:2018/08/31 14:33
  • ACB How to use MCR

    It is special relay characteristic for selective co-ordination. When closing ACB (changing from OFF to ON), the instantaneous tripping characteristic is effe... More Details >>

    • No:22402
    • Release Date:2018/08/31 14:33
  • ACB terminal connection

    Horizontal connection type (standard: AE-SW up to 3200A except 2000-SWA), Vertical connection (VT) type (standard: 2000-SWA,4000-SWA -6300-SW) and Front conn... More Details >>

    • No:22417
    • Release Date:2018/08/31 14:33
  • replace AE-SS with AE-SW

    (1) and (2) are impossible. More Details >>

    • No:24818
    • Release Date:2019/04/09 15:03

11-20 of Total 23