FAQ


FAQAbout Products

- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers > Air Circuit Breakers
FAQ
Keyword Search
FAQ within [ Air Circuit Breakers ]
-
For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>
- No:22418
- Release Date:2018/08/31 14:33
-
For ACB, Line and Load are not defined on the main circuit terminals. Reverse connection is available without any limitation. More Details >>
- No:22425
- Release Date:2018/08/31 14:33
-
Drawout type circuit breaker can be drawn-out and insert to the cradle without taking out the connecting conductor. As ACB is drawn out, it will be "connect ... More Details >>
- No:22431
- Release Date:2018/08/31 14:33
-
It is not possible to use standard AE-SW in DC circuit. Special DC use AE-SW is provided if specified. More Details >>
- No:22446
- Release Date:2018/08/31 14:33
-
The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>
- No:22440
- Release Date:2018/08/31 14:33
-
Horizontal connection type (standard: AE-SW up to 3200A except 2000-SWA), Vertical connection (VT) type (standard: 2000-SWA,4000-SWA -6300-SW) and Front conn... More Details >>
- No:22417
- Release Date:2018/08/31 14:33
-
Horizontal allowable distance when installing ACB
Flatness of mounting plane: 1 mm or less.In addition, it is necessary to consider the horizontality of the panel. More Details >>
- No:37698
- Release Date:2020/01/17 17:32
-
Generally, there is no Mechanical Trip indication of continuous output for AE-SW. It is necessary to indicate electrically by using OCR Alarm (AL) output or ... More Details >>
- No:22432
- Release Date:2018/08/31 14:33
-
Ground fault protection (GFR) is prepared as option, it is possible to detect and protect against ground fault current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22412
- Release Date:2018/08/31 14:33
-
The test position is a position where a main circuit is in the "disconnected" state and only control circuit is in the "connected" state. Control circuit che... More Details >>
- No:22405
- Release Date:2018/08/31 14:33
11-20 of Total 23