FAQ within [ Air Circuit Breakers ]

11-20 of Total 23

prev 2 / 3page next
  • ACB How to check the operating characteristic

    Y-2005 type field test equipment (it is sold separately) enable to check the operating characteristic easily. The test is conducted by connecting the test te... More Details >>

    • No:22429
    • Release Date:2018/08/31 14:33
  • ACB opening time

    For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>

    • No:22418
    • Release Date:2018/08/31 14:33
  • ACB Shorting B contact (SBC)

    This contact(SBC) is used to auxiliary switch(AXb) contact. When Drawout type ACB is moved from "test" position to "disconnect" position, AXb contact will b... More Details >>

    • No:22416
    • Release Date:2018/08/31 14:33
  • ACB test position

    The test position is a position where a main circuit is in the "disconnected" state and only control circuit is in the "connected" state. Control circuit che... More Details >>

    • No:22405
    • Release Date:2018/08/31 14:33
  • Horizontal allowable distance when installing ACB

    Flatness of mounting plane: 1 mm or less.In addition, it is necessary to consider the horizontality of the panel. More Details >>

    • No:37698
    • Release Date:2020/01/17 17:32
  • Setting change operation while power is on

    It is forbidden to change the characteristic when the breaker ON. Over current trip and earth leakage trip characteristics should be changed by a person with... More Details >>

    • No:37699
    • Release Date:2020/01/18 09:58
  • ACB trip indication

    Generally, there is no Mechanical Trip indication of continuous output for AE-SW. It is necessary to indicate electrically by using OCR Alarm (AL) output or ... More Details >>

    • No:22432
    • Release Date:2018/08/31 14:33
  • Release element in neutral (4P breaker)

    AE-SW 4-poles with WS relay (general protection) has overcurrent protection for neutral-pole. The tripping characteristic is same as phase-pole. Moreover, A... More Details >>

    • No:22441
    • Release Date:2018/08/31 14:33
  • ACB DC use

    It is not possible to use standard AE-SW in DC circuit. Special DC use AE-SW is provided if specified. More Details >>

    • No:22446
    • Release Date:2018/08/31 14:33
  • ACB installation type

    There are Fixed type and Drawout type. More Details >>

    • No:22430
    • Release Date:2018/08/31 14:33