ACB How to check the operating characteristic
Y-2005 type field test equipment (it is sold separately) enable to check the operating characteristic easily. The test is conducted by connecting the test te... More Details >>
- No:22429
- Release Date:2018/08/31 14:33
-
ACB General use Generator protection use
General protection relay (WS) of AE-SW type Air Circuit Breaker has tripping characteristic and function for general use. However, we also provide the replay... More Details >>
- No:22414
- Release Date:2018/08/31 14:33
-
Release element in neutral (4P breaker)
AE-SW 4-poles with WS relay (general protection) has overcurrent protection for neutral-pole. The tripping characteristic is same as phase-pole. Moreover, A... More Details >>
- No:22441
- Release Date:2018/08/31 14:33
-
(1) and (2) are impossible. More Details >>
- No:24818
- Release Date:2019/04/09 15:03
-
For ACB, Line and Load are not defined on the main circuit terminals. Reverse connection is available without any limitation. More Details >>
- No:22425
- Release Date:2018/08/31 14:33
-
Generally, there is no Mechanical Trip indication of continuous output for AE-SW. It is necessary to indicate electrically by using OCR Alarm (AL) output or ... More Details >>
- No:22432
- Release Date:2018/08/31 14:33
-
For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>
- No:22418
- Release Date:2018/08/31 14:33
-
It is not possible to use standard AE-SW in DC circuit. Special DC use AE-SW is provided if specified. More Details >>
- No:22446
- Release Date:2018/08/31 14:33
-
Horizontal allowable distance when installing ACB
Flatness of mounting plane: 1 mm or less.In addition, it is necessary to consider the horizontality of the panel. More Details >>
- No:37698
- Release Date:2020/01/17 17:32
-
ACB combination Ground fault protection and earth leakage protection
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
- No:22419
- Release Date:2018/08/31 14:33