FAQ within [ Air Circuit Breakers ]
-
It is special relay characteristic for selective co-ordination. When closing ACB (changing from OFF to ON), the instantaneous tripping characteristic is effe... More Details >>
- No:22402
- Release Date:2018/08/31 14:33
-
The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>
- No:22440
- Release Date:2018/08/31 14:33
-
Rated current and continuous current
The rated current is standard value for continuous current, short time delay current and instantaneous current. Continuous current is non-breaking current (c... More Details >>
- No:22371
- Release Date:2018/08/31 14:33
-
(1) and (2) are impossible. More Details >>
- No:24818
- Release Date:2019/04/09 15:03
-
Drawout type circuit breaker can be drawn-out and insert to the cradle without taking out the connecting conductor. As ACB is drawn out, it will be "connect ... More Details >>
- No:22431
- Release Date:2018/08/31 14:33
-
ACB General use Generator protection use
General protection relay (WS) of AE-SW type Air Circuit Breaker has tripping characteristic and function for general use. However, we also provide the replay... More Details >>
- No:22414
- Release Date:2018/08/31 14:33
-
ACB combination Ground fault protection and earth leakage protection
It is not possible to combine them at the same time. You need to choose one of them. More Details >>
- No:22419
- Release Date:2018/08/31 14:33
-
It is a standard equipment (automatic reset type) and 30ms of one-pulse is output at overload tripping. Hold-type circuit is necessary since the output time ... More Details >>
- No:22428
- Release Date:2018/08/31 14:33
-
Ground fault protection (GFR) is prepared as option, it is possible to detect and protect against ground fault current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22412
- Release Date:2018/08/31 14:33
-
ACB add earth leakage protection
When earth leakage current protection module (ER) is attached, it is possible to protect against earth leakage current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22420
- Release Date:2018/08/31 14:33