The range of ambient temperature is from -10 to 40 degree Celsius for not only MCCB but also including Earth Leakage Circuit breaker, Earth Leakage Relay and... More Details >>
- No:22352
- Release Date:2018/08/31 14:33
-
It is a button in order to mechanically trip a circuit breaker outside. It is used to confirm switching mechanism at the regular maintenance or sequence-chec... More Details >>
- No:22368
- Release Date:2018/08/31 14:33
-
Electronic MCCB 400-1600A How to change rated current and characteristic curve (Except CE breakers)
First, turn OFF the upstream circuit breaker and the relevant circuit breaker. You must not work in the state where voltage is applied to the relevant circui... More Details >>
- No:22439
- Release Date:2018/08/31 14:33
- Update:2018/08/31 14:35
-
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
- No:22401
- Release Date:2018/08/31 14:33
-
IEC 60947-2 is an international standard for circuit breakers. The rated voltage for the applicable circuit breaker is 1000V AC or less, or DC 1500V DC or le... More Details >>
- No:22361
- Release Date:2018/08/31 14:33
-
It is a button in order to trip MCCB. It is used for regular inspection of the switching mechanism, and trip condition of MCCB when Alarm switch (AL) and Shu... More Details >>
- No:22444
- Release Date:2018/08/31 14:33
-
Operating characteristics described in our catalog (if there is no "Note" particularly) mean operating time when it starts to carry current from the conditio... More Details >>
- No:22374
- Release Date:2018/08/31 14:33
-
If switching of neutral pole is not needed, it is possible to use 3-pole MCCB for 3-phase 4- wire circuit. Generally, it is recommended to use 4-pole circuit... More Details >>
- No:22385
- Release Date:2018/08/31 14:33
-
Inverse time delay operating characteristic
It is a characteristic that operating time inversely become shorter as current increases. For Molded Case Circuit Breakers, protection characteristic meeting... More Details >>
- No:22387
- Release Date:2018/08/31 14:33
-
AC Breakers used at DC circuit
It is not possible to use a circuit breaker for AC in DC circuit. Since the Arc-Extinguishing Device structure of circuit breaker for DC is different from th... More Details >>
- No:22381
- Release Date:2018/08/31 14:33