FAQ within [ Molded Case Circuit Breakers ]

11-20 of Total 49

prev 2 / 5page next
  • MCCB and MCB as terms

    MCCB stands for "Molded Case Circuit Breaker." This is defined in the IEC standard, IEC 60947-2 and in the UL standard, UL 489. MCB stands for "Miniature Ci... More Details >>

    • No:22340
    • Release Date:2018/08/31 14:33
  • Calorific value of the circuit breaker

    1. The internal resistance (per pole) is described in the catalog and technical notes. 2. Power consumption (W) = RI^2 x Poles = Resistance (Ω) x Load curre... More Details >>

    • No:38025
    • Release Date:2021/01/22 17:39
  • How to connect to 2-pole breaker

    (1) When "N" is marked on the breaker,connect the N phase wire as marked. (2) When "N" is not marked on the breaker, N phase wire can be connected to eith... More Details >>

    • No:37700
    • Release Date:2020/01/17 08:58
  • Storage temperature range of MCCBs and ELCBs

    It is from -25 to 55℃ in Trip or OFF position. However, it shall be in an environment without condensation and freezing even in a short time. More Details >>

    • No:22426
    • Release Date:2018/08/31 14:33
  • How to fix conductors/wires

    Large electromagnetic force will be generated between conductors/wires due to fault currents. To prevent deformation and breakage of circuit breakers and con... More Details >>

    • No:22424
    • Release Date:2018/08/31 14:33
  • Inst tripping current value of AC/DC common breaker

    At time-delay tripping zone, it operates with bimetal, therefore the characteristics of AC and DC should be same if the effective values of them are same. Ho... More Details >>

    • No:22392
    • Release Date:2018/08/31 14:33
  • Inverse time delay operating characteristic

    It is a characteristic that operating time inversely become shorter as current increases. For Molded Case Circuit Breakers, protection characteristic meeting... More Details >>

    • No:22387
    • Release Date:2018/08/31 14:33
  • MCCB 3P4W 3P use

    If switching of neutral pole is not needed, it is possible to use 3-pole MCCB for 3-phase 4- wire circuit. Generally, it is recommended to use 4-pole circuit... More Details >>

    • No:22385
    • Release Date:2018/08/31 14:33
  • Arc space

    It means a space between the edge of a exhaust port and panel component ( such as wall or duct) of a circuit breaker. The arc space is needed for smoothly di... More Details >>

    • No:22373
    • Release Date:2018/08/31 14:33
  • Instantaneous tripping

    It is a tripping zone which instantly trips, when significantly overcurrent such as short-circuit currents flow. More Details >>

    • No:22363
    • Release Date:2018/08/31 14:33