FAQ


FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers > Molded Case Circuit Breakers
FAQ
Keyword Search
FAQ within [ Molded Case Circuit Breakers ]
-
No, you must not use 2-pole circuit breaker as 1-pole circuit breaker (series connection as only single phase ). If using it as 1-pole circuit breaker, these... More Details >>
- No:22382
- Release Date:2018/08/31 14:33
-
AC Breakers used at DC circuit
It is not possible to use a circuit breaker for AC in DC circuit. Since the Arc-Extinguishing Device structure of circuit breaker for DC is different from th... More Details >>
- No:22381
- Release Date:2018/08/31 14:33
-
Electronic MCCB 400-1600A How to change rated current and characteristic curve (Except CE breakers)
First, turn OFF the upstream circuit breaker and the relevant circuit breaker. You must not work in the state where voltage is applied to the relevant circui... More Details >>
- No:22439
- Release Date:2018/08/31 14:33
- Update:2018/08/31 14:35
-
It is possible to attach closely if there is no problem about the insulation distance between live parts such as a terminal bar and load currents are 80% or ... More Details >>
- No:22400
- Release Date:2018/08/31 14:33
-
It is the maximum voltage which meets the performance criteria for the rated operational voltage. More Details >>
- No:22367
- Release Date:2018/08/31 14:33
-
If switching of neutral pole is not needed, it is possible to use 3-pole MCCB for 3-phase 4- wire circuit. Generally, it is recommended to use 4-pole circuit... More Details >>
- No:22385
- Release Date:2018/08/31 14:33
-
It means a space between the edge of a exhaust port and panel component ( such as wall or duct) of a circuit breaker. The arc space is needed for smoothly di... More Details >>
- No:22373
- Release Date:2018/08/31 14:33
-
How to select at Inverter circuit
Basically you have to consider the effect of harmonic waves, but there are two ways as below. 1. Refer to the recommended rated current by inverter manufactu... More Details >>
- No:22360
- Release Date:2018/08/31 14:33
-
How to install cassette type accessories
A circuit breaker shall be Trip position when installing Cassette type accessory. The breaker may be damaged if installing in "ON" or "OFF" position. Moreove... More Details >>
- No:22422
- Release Date:2018/08/31 14:33
-
It is possible to modify to Rear-connection type by Mitsubishi's certified staff. More Details >>
- No:22399
- Release Date:2018/08/31 14:33
11-20 of Total 49