How to select at Inverter circuit
Basically you have to consider the effect of harmonic waves, but there are two ways as below. 1. Refer to the recommended rated current by inverter manufactu... More Details >>
- No:22360
- Release Date:2018/08/31 14:33
-
How to connect to 2-pole breaker
(1) When "N" is marked on the breaker,connect the N phase wire as marked. (2) When "N" is not marked on the breaker, N phase wire can be connected to eith... More Details >>
- No:37700
- Release Date:2020/01/17 08:58
-
Change Electronic relay characteristics when it is energized
Only electricians who have enough technical knowledge should change the setting of overcurrent tripping and earth leakage tripping characteristics. Moreover,... More Details >>
- No:22409
- Release Date:2018/08/31 14:33
-
It is a protection method which only trips the related circuit breaker and other fault-free circuit does not trip and continues power supply in the event of... More Details >>
- No:22366
- Release Date:2018/08/31 14:33
-
Operating characteristics described in our catalog (if there is no "Note" particularly) mean operating time when it starts to carry current from the conditio... More Details >>
- No:22374
- Release Date:2018/08/31 14:33
-
Max. operational voltage for AC/DC Common
When it is connected as special connection, AC/DC compatible circuit breaker can be used with DC 250V or more (3-pole type is DC400V and 4-pole type is DC500... More Details >>
- No:22445
- Release Date:2018/08/31 14:33
-
How to install cassette type accessories
A circuit breaker shall be Trip position when installing Cassette type accessory. The breaker may be damaged if installing in "ON" or "OFF" position. Moreove... More Details >>
- No:22422
- Release Date:2018/08/31 14:33
-
Default setting of electronic breakers
Each setting knob of the overcurrent trip characteristic is set to the maximum value and then shipped if not specified. However, only the pre-alarm is set to... More Details >>
- No:22438
- Release Date:2018/08/31 14:33
-
MCCB, ELCB and ACB at higher altitudes
In that case, the rated current and the rated voltage shall be reduced. Refer to the table of derating factors as below. More Details >>
- No:24801
- Release Date:2019/04/09 15:17
-
It is possible to modify to Rear-connection type by Mitsubishi's certified staff. More Details >>
- No:22399
- Release Date:2018/08/31 14:33