  • degrees of protection to  IEC60529

    The degess of protection for ACB is IP20 as standard (under the condition that front door is closed). For MCCB and ELCB, the degrees of protection can be IP2... More Details >>

    • No:24812
    • Release Date:2019/04/09 15:18
  • Side by side installation

    It is possible to attach closely if there is no problem about the insulation distance between live parts such as a terminal bar and load currents are 80% or ... More Details >>

    • No:22400
    • Release Date:2018/08/31 14:33
  • Ambient temperature

    The range of ambient temperature is from -10 to 40 degree Celsius for not only MCCB but also including Earth Leakage Circuit breaker, Earth Leakage Relay and... More Details >>

    • No:22352
    • Release Date:2018/08/31 14:33
  • Max. operational voltage for AC/DC Common

    When it is connected as special connection, AC/DC compatible circuit breaker can be used with DC 250V or more (3-pole type is DC400V and 4-pole type is DC500... More Details >>

    • No:22445
    • Release Date:2018/08/31 14:33
  • Storage temperature range of MCCBs and ELCBs

    It is from -25 to 55℃ in Trip or OFF position. However, it shall be in an environment without condensation and freezing even in a short time. More Details >>

    • No:22426
    • Release Date:2018/08/31 14:33
  • Operational voltage

    It is the maximum voltage which meets the performance criteria for the rated operational voltage. More Details >>

    • No:22367
    • Release Date:2018/08/31 14:33
  • Plug-in type NF1600-SEW produced

    It is impossible. More Details >>

    • No:24817
    • Release Date:2019/04/09 15:16
  • Selective coordination

    It is a protection method which only trips the related circuit breaker and other fault-free circuit does not trip and continues power supply in the event of... More Details >>

    • No:22366
    • Release Date:2018/08/31 14:33
  • MCCB bar terminal material

    Bar terminal material for 400A is aluminum alloy, and for 630A or higher is copper. More Details >>

    • No:24819
    • Release Date:2019/04/09 15:13
  • IEC60947-2 standard

    IEC 60947-2 is an international standard for circuit breakers. The rated voltage for the applicable circuit breaker is 1000V AC or less, or DC 1500V DC or le... More Details >>