  • lower limit of operational voltage for DC

    It is DC 24V. More Details >>

    • No:24816
    • Release Date:2019/04/09 15:17
  • How to select at Inverter circuit

    Basically you have to consider the effect of harmonic waves, but there are two ways as below. 1. Refer to the recommended rated current by inverter manufactu... More Details >>

    • No:22360
    • Release Date:2018/08/31 14:33
  • Wrong connection in reverse

    It may not trip a fault current or degrade insulation after tripping. When you connect the device in reverse, you must select a reverse-connectable model. More Details >>

    • No:22345
    • Release Date:2018/08/31 14:33
  • Rated insulation voltage

    It is voltage which ensures withstand voltage and it is used as basis to determine insulation distance. More Details >>

    • No:22362
    • Release Date:2018/08/31 14:33
  • How to use Trip button

    It is a button in order to trip MCCB. It is used for regular inspection of the switching mechanism, and trip condition of MCCB when Alarm switch (AL) and Shu... More Details >>

    • No:22444
    • Release Date:2018/08/31 14:33
  • 2P MCCB only 1-pole use

    No, you must not use 2-pole circuit breaker as 1-pole circuit breaker (series connection as only single phase ). If using it as 1-pole circuit breaker, these... More Details >>

    • No:22382
    • Release Date:2018/08/31 14:33
  • Max. operational voltage for AC/DC Common

    When it is connected as special connection, AC/DC compatible circuit breaker can be used with DC 250V or more (3-pole type is DC400V and 4-pole type is DC500... More Details >>

    • No:22445
    • Release Date:2018/08/31 14:33
  • Interrupting ratings

    A circuit breaker must have interrupting ratings. These are classified as rated short-circuit breaking capacities in IEC 60947-2.e rated ultimate short-circu... More Details >>

    • No:22341
    • Release Date:2018/08/31 14:33
  • Use in 40℃~60℃

    Operating ambient temperature is set to - 10℃ to 40℃. ( However, its average over a period of 24h does not exceed 35℃.) In the case that the ambient temperat... More Details >>

    • No:22370
    • Release Date:2018/08/31 14:33
  • Calorific value of the circuit breaker

    1. The internal resistance (per pole) is described in the catalog and technical notes. 2. Power consumption (W) = RI^2 x Poles = Resistance (Ω) x Load curre... More Details >>

    • No:38025
    • Release Date:2021/01/22 17:39