FAQ


FAQAbout Products

- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers > Molded Case Circuit Breakers
FAQ
Keyword Search
FAQ within [ Molded Case Circuit Breakers ]
-
Operating ambient temperature is set to - 10℃ to 40℃. ( However, its average over a period of 24h does not exceed 35℃.) In the case that the ambient temperat... More Details >>
- No:22370
- Release Date:2018/08/31 14:33
-
AC Breakers used at DC circuit
It is not possible to use a circuit breaker for AC in DC circuit. Since the Arc-Extinguishing Device structure of circuit breaker for DC is different from th... More Details >>
- No:22381
- Release Date:2018/08/31 14:33
-
It is possible to attach closely if there is no problem about the insulation distance between live parts such as a terminal bar and load currents are 80% or ... More Details >>
- No:22400
- Release Date:2018/08/31 14:33
-
It is a button in order to mechanically trip a circuit breaker outside. It is used to confirm switching mechanism at the regular maintenance or sequence-chec... More Details >>
- No:22368
- Release Date:2018/08/31 14:33
-
Calorific value of the circuit breaker
1. The internal resistance (per pole) is described in the catalog and technical notes. 2. Power consumption (W) = RI^2 x Poles = Resistance (Ω) x Load curre... More Details >>
- No:38025
- Release Date:2021/01/22 17:39
-
IEC 60947-2 is an international standard for circuit breakers. The rated voltage for the applicable circuit breaker is 1000V AC or less, or DC 1500V DC or le... More Details >>
- No:22361
- Release Date:2018/08/31 14:33
-
It is voltage which ensures withstand voltage and it is used as basis to determine insulation distance. More Details >>
- No:22362
- Release Date:2018/08/31 14:33
-
Almost MCCBs can be connected n reverse. Check the item column of specification table "reverse connection" in the catalog. If it says "Possible", MCCB can be... More Details >>
- No:22442
- Release Date:2018/08/31 14:33
-
The range of ambient temperature is from -10 to 40 degree Celsius for not only MCCB but also including Earth Leakage Circuit breaker, Earth Leakage Relay and... More Details >>
- No:22352
- Release Date:2018/08/31 14:33
-
It means a space between the edge of a exhaust port and panel component ( such as wall or duct) of a circuit breaker. The arc space is needed for smoothly di... More Details >>
- No:22373
- Release Date:2018/08/31 14:33
31-40 of Total 49