FAQ within [ Molded Case Circuit Breakers ]

1-10 of Total 49

prev 1 / 5page next
  • Trip button

    It is a button in order to mechanically trip a circuit breaker outside. It is used to confirm switching mechanism at the regular maintenance or sequence-chec... More Details >>

    • No:22368
    • Release Date:2018/08/31 14:33
  • Setting change operation while power is on

    It is forbidden to change the characteristic when the breaker ON. Over current trip and earth leakage trip characteristics should be changed by a person with... More Details >>

    • No:37699
    • Release Date:2020/01/18 09:58
  • Use in 40℃~60℃

    Operating ambient temperature is set to - 10℃ to 40℃. ( However, its average over a period of 24h does not exceed 35℃.) In the case that the ambient temperat... More Details >>

    • No:22370
    • Release Date:2018/08/31 14:33
  • How to fix conductors/wires

    Large electromagnetic force will be generated between conductors/wires due to fault currents. To prevent deformation and breakage of circuit breakers and con... More Details >>

    • No:22424
    • Release Date:2018/08/31 14:33
  • Minimum operating voltage

    Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>

    • No:22401
    • Release Date:2018/08/31 14:33
  • MCCB and MCB as terms

    MCCB stands for "Molded Case Circuit Breaker." This is defined in the IEC standard, IEC 60947-2 and in the UL standard, UL 489. MCB stands for "Miniature Ci... More Details >>

    • No:22340
    • Release Date:2018/08/31 14:33
  • Rating of a circuit breaker for transformers primary protection

    When making a transformer to energize, a large inrush current may flow. The circuit breaker is therefore required to prevent unwanted trip. The selection of ... More Details >>

    • No:22343
    • Release Date:2018/08/31 14:33
  • How to use Trip button

    It is a button in order to trip MCCB. It is used for regular inspection of the switching mechanism, and trip condition of MCCB when Alarm switch (AL) and Shu... More Details >>

    • No:22444
    • Release Date:2018/08/31 14:33
  • 2P MCCB only 1-pole use

    No, you must not use 2-pole circuit breaker as 1-pole circuit breaker (series connection as only single phase ). If using it as 1-pole circuit breaker, these... More Details >>

    • No:22382
    • Release Date:2018/08/31 14:33
  • Switch disconnector

    Switch disconnector is a switch compatible with IEC 60947-3 standard, and it has no overcurrent tripping element. Please use it as a switch with large switch... More Details >>

    • No:22379
    • Release Date:2018/08/31 14:33