FAQ
FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers > Earth Leakage Circuit Breakers
FAQ
Keyword Search
FAQ within [ Earth Leakage Circuit Breakers ]
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of 30mA or less. More Details >>
- No:22390
- Release Date:2018/08/31 14:33
-
The applicable voltage is 440V or less. Moreover, High-speed type can be used from 85 to 484V, and Time-delay type can be used from 170 to 484V. More Details >>
- No:22421
- Release Date:2018/08/31 14:33
-
Select rated current sensitivity
Please select rated current sensitivity ,according to the protection purpose and the protective grounding resistance value of the load equipment. If you alre... More Details >>
- No:22346
- Release Date:2018/08/31 14:33
-
The push button is used for testing whether it definitely trips when an earth leakage current occurs. At this test, a Leakage Display button will be come out... More Details >>
- No:22347
- Release Date:2018/08/31 14:33
-
The circuit breaker is designed to attain a predetermined value of limiting non-actuating time corresponding to a given value of residual current. Our time-d... More Details >>
- No:22351
- Release Date:2018/08/31 14:33
-
It is same as the maximum rated operational voltage. More Details >>
- No:22365
- Release Date:2018/08/31 14:33
-
High-speed residual operate CBR
It is Earth Leakage Circuit Breaker that the earth leakage trip operating time at the rated residual operating current (IΔn) is within 0.1 sec, and the earth... More Details >>
- No:22380
- Release Date:2018/08/31 14:33
-
Earth Leakage Circuit Breaker and Earth Leakage Relay operate at higher than 50% but not exceeding 100% of the rated residual operating current IΔn. The eart... More Details >>
- No:22364
- Release Date:2018/08/31 14:33
-
Earth leakage protective coordination
Since the total electric circuit length of upstream circuit breaker side is longer than that of downstream circuit breaker, constant earth leakage current b... More Details >>
- No:22369
- Release Date:2018/08/31 14:33
-
Default setting from the factory
The knob of the sensitivity current selector is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage... More Details >>
- No:22391
- Release Date:2018/08/31 14:33
1-10 of Total 21