FAQ within [ Earth Leakage Circuit Breakers ]
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of 30mA or less. More Details >>
- No:22390
- Release Date:2018/08/31 14:33
-
4-pole type in 100VAC or 110VAC
The rated operational voltages for them are 200 to 440VAC. If using them in 100VAC or 110VAC circuit, earth-leakage protection does not operate. More Details >>
- No:24820
- Release Date:2019/04/09 15:10
-
Earth leakage protective coordination
Since the total electric circuit length of upstream circuit breaker side is longer than that of downstream circuit breaker, constant earth leakage current b... More Details >>
- No:22369
- Release Date:2018/08/31 14:33
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of higher than 30mA but not exceeding 1000mA. We provide the products of "100, ... More Details >>
- No:22395
- Release Date:2018/08/31 14:33
-
ELCB applicable to harmonics and surge
Compared with general circuit breakers, Earth Leakage Circuit Breaker applicable to harmonics and surge has earth leakage current detecting characteristic wh... More Details >>
- No:22344
- Release Date:2018/08/31 14:33
-
It is an earth leakage current (Effective value of residual operating current) which definitely trips Earth Leakage Circuit Breaker and Earth Leakage Relay ... More Details >>
- No:22353
- Release Date:2018/08/31 14:33
-
Time Delay type at the maximum operating time
The maximum operating time of Time-delay type Earth Leakage Circuit Breaker can be switched to 0.45s, 1.0s and 2.0s. The operating time is:* when it is 0.45s... More Details >>
- No:22375
- Release Date:2018/08/31 14:33
-
Almost ELCBs can be connected n reverse. Check the item column of specification table "reverse connection (below 230 V AC)" in the catalog. If it says "Possi... More Details >>
- No:22434
- Release Date:2018/08/31 14:33
-
Residual non-operating current
It is a current that does not leak-trip even if there is ground fault current or leakage current. In the standard, it is 50 % of the rated residual operating... More Details >>
- No:22356
- Release Date:2018/08/31 14:33
-
It is possible to use it if you connect with right and left poles, not neutral pole. Since electronic circuit power supply for earth leakage detection is tak... More Details >>
- No:22359
- Release Date:2018/08/31 14:33
11-20 of Total 21