FAQ within [ Earth Leakage Circuit Breakers ]
-
Default setting from the factory
The knob of the sensitivity current selector is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage... More Details >>
- No:22391
- Release Date:2018/08/31 14:33
-
Earth Leakage Circuit Breaker and Earth Leakage Relay operate at higher than 50% but not exceeding 100% of the rated residual operating current IΔn. The eart... More Details >>
- No:22364
- Release Date:2018/08/31 14:33
-
Residual non-operating current
It is a current that does not leak-trip even if there is ground fault current or leakage current. In the standard, it is 50 % of the rated residual operating... More Details >>
- No:22356
- Release Date:2018/08/31 14:33
-
It is an earth leakage current (Effective value of residual operating current) which definitely trips Earth Leakage Circuit Breaker and Earth Leakage Relay ... More Details >>
- No:22353
- Release Date:2018/08/31 14:33
-
Almost ELCBs can be connected n reverse. Check the item column of specification table "reverse connection (below 230 V AC)" in the catalog. If it says "Possi... More Details >>
- No:22434
- Release Date:2018/08/31 14:33
-
High-speed residual operate CBR
It is Earth Leakage Circuit Breaker that the earth leakage trip operating time at the rated residual operating current (IΔn) is within 0.1 sec, and the earth... More Details >>
- No:22380
- Release Date:2018/08/31 14:33
-
The control power supply of the earth leakage detection circuit is taken from the inside of Earth Leakage Circuit Breaker. If used on the secondary side of t... More Details >>
- No:22372
- Release Date:2018/08/31 14:33
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of 30mA or less. More Details >>
- No:22390
- Release Date:2018/08/31 14:33
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of higher than 30mA but not exceeding 1000mA. We provide the products of "100, ... More Details >>
- No:22395
- Release Date:2018/08/31 14:33
-
It is possible to reverse-connect if the circuit voltage of UL789 listed products is AC240V or less. Since they are double standard products of UL/CSA and CE... More Details >>
- No:22411
- Release Date:2018/08/31 14:33