- FAQ > Low-voltage Power Distribution Products > Low-voltage Circuit Breakers > Earth Leakage Circuit Breakers
FAQ
Keyword Search
FAQ within [ Earth Leakage Circuit Breakers ]
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of higher than 30mA but not exceeding 1000mA. We provide the products of "100, ... More Details >>
- No:22395
- Release Date:2018/08/31 14:33
-
Time Delay type at the maximum operating time
The maximum operating time of Time-delay type Earth Leakage Circuit Breaker can be switched to 0.45s, 1.0s and 2.0s. The operating time is:* when it is 0.45s... More Details >>
- No:22375
- Release Date:2018/08/31 14:33
-
Earth Leakage Circuit Breaker and Earth Leakage Relay operate at higher than 50% but not exceeding 100% of the rated residual operating current IΔn. The eart... More Details >>
- No:22364
- Release Date:2018/08/31 14:33
-
Select rated current sensitivity
Please select rated current sensitivity ,according to the protection purpose and the protective grounding resistance value of the load equipment. If you alre... More Details >>
- No:22346
- Release Date:2018/08/31 14:33
-
4-pole type in 100VAC or 110VAC
The rated operational voltages for them are 200 to 440VAC. If using them in 100VAC or 110VAC circuit, earth-leakage protection does not operate. More Details >>
- No:24820
- Release Date:2019/04/09 15:10
-
The applicable voltage is 440V or less. Moreover, High-speed type can be used from 85 to 484V, and Time-delay type can be used from 170 to 484V. More Details >>
- No:22421
- Release Date:2018/08/31 14:33
-
It is possible to reverse-connect if the circuit voltage of UL789 listed products is AC240V or less. Since they are double standard products of UL/CSA and CE... More Details >>
- No:22411
- Release Date:2018/08/31 14:33
-
Default setting from the factory
The knob of the sensitivity current selector is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage... More Details >>
- No:22391
- Release Date:2018/08/31 14:33
-
It is the Earth Leakage Circuit Breaker with rated residual operating current of 30mA or less. More Details >>
- No:22390
- Release Date:2018/08/31 14:33
-
High-speed residual operate CBR
It is Earth Leakage Circuit Breaker that the earth leakage trip operating time at the rated residual operating current (IΔn) is within 0.1 sec, and the earth... More Details >>
- No:22380
- Release Date:2018/08/31 14:33