  • Default setting from the factory

    The knob of the sensitivity current selector is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage... More Details >>

    • No:22391
    • Release Date:2018/08/31 14:33
  • Rated current sensitivity

    Earth Leakage Circuit Breaker and Earth Leakage Relay operate at higher than 50% but not exceeding 100% of the rated residual operating current IΔn. The eart... More Details >>

    • No:22364
    • Release Date:2018/08/31 14:33
  • High-speed residual operate CBR

    It is Earth Leakage Circuit Breaker that the earth leakage trip operating time at the rated residual operating current (IΔn) is within 0.1 sec, and the earth... More Details >>

    • No:22380
    • Release Date:2018/08/31 14:33
  • ELCB Rated insulation voltage

    It is same as the maximum rated operational voltage. More Details >>

    • No:22365
    • Release Date:2018/08/31 14:33
  • Rated current sensitivity

    It is an earth leakage current (Effective value of residual operating current) which definitely trips Earth Leakage Circuit Breaker and Earth Leakage Relay ... More Details >>

    • No:22353
    • Release Date:2018/08/31 14:33
  • ELCB reverse connection

    Almost ELCBs can be connected n reverse. Check the item column of specification table "reverse connection (below 230 V AC)" in the catalog. If it says "Possi... More Details >>

    • No:22434
    • Release Date:2018/08/31 14:33
  • Earth leakage protective coordination

    Since the total electric circuit length of upstream circuit breaker side is longer than that of downstream circuit breaker, constant earth leakage current b... More Details >>

    • No:22369
    • Release Date:2018/08/31 14:33
  • ELCB installation

    The control power supply of the earth leakage detection circuit is taken from the inside of Earth Leakage Circuit Breaker. If used on the secondary side of t... More Details >>

    • No:22372
    • Release Date:2018/08/31 14:33
  • ELCB medium-sensitivity

    It is the Earth Leakage Circuit Breaker with rated residual operating current of higher than 30mA but not exceeding 1000mA. We provide the products of "100, ... More Details >>

    • No:22395
    • Release Date:2018/08/31 14:33
  • ELCB applicable voltage

    The applicable voltage is 440V or less. Moreover, High-speed type can be used from 85 to 484V, and Time-delay type can be used from 170 to 484V. More Details >>

    • No:22421
    • Release Date:2018/08/31 14:33