FAQ within [ Motor Starters ]
-
About Low-voltage Power Distribution Products
A thermal load relay is set as full-load current of a motor. However, ifambient temperature is significantly different from 20℃ or the connectingwire is diff... More Details >>
- No:23238
- Release Date:2018/09/12 15:11
-
About Low-voltage Power Distribution Products
It is utilization category specified in IEC 60947-4-1. AC-4 category is usedfor inching or plugging etc. More Details >>
- No:23250
- Release Date:2018/09/12 15:11
-
About Low-voltage Power Distribution Products
It is a current value that can break ( turning contact "OFF") under theconditions specified in the standard. (In IEC, number of tests is 50 times) More Details >>
- No:23261
- Release Date:2018/09/12 15:11
-
About Low-voltage Power Distribution Products
You can install it as follows.1. Regular installation of the power supply side terminal as the upper partand the load side terminal as the lower side2. Incli... More Details >>
- No:23283
- Release Date:2018/09/12 15:11
-
About Low-voltage Power Distribution Products
It is a magnetic contactor that can reverse a motor by using two magneticcontactors and switching the connection of their contacts. More Details >>
- No:23287
- Release Date:2018/09/12 15:11
-
About Low-voltage Power Distribution Products
Since US-N/K/H type is a solid state contactor having zero-voltage-triggering method, surge voltage does not occur due to opening/closing amain circuit. More... More Details >>
- No:23291
- Release Date:2018/09/12 15:11
-
About Low-voltage Power Distribution Products
It is necessary to change the wires connected by solder to the board of theDL circuit since the wire length is short. Therefore, it is not possible toconnect... More Details >>
- No:23299
- Release Date:2018/09/12 15:11
-
About Low-voltage Power Distribution Products
The fault detection contact of the cooling fan detects the temperature ofthe fin in the solid state contactor and operates when exceeding thespecified value.... More Details >>
- No:23301
- Release Date:2018/09/12 15:11
-
About Low-voltage Power Distribution Products
The maximum ambient temparature for US-N/K/H type is 60℃ and theycan not be used with more than 60℃. If the temparature is more than60℃, you need to consider... More Details >>
- No:23346
- Release Date:2018/09/12 15:12
-
About Low-voltage Power Distribution Products
Bearing lifetime of cooling fan is 10,000 to 35,000 hours. However, thelifetime of the cooling fan will be reduced depending on the ambienttemperature rise, ... More Details >>
- No:23364
- Release Date:2018/09/12 15:12