FAQ within [ Low-voltage Power Distribution Products ]
-
Error in the measurement value (ME96SS series).
There is a possibility of the wiring error for VT/CT to this model. Please check the wiring for VT/CT and this model. More Details >>
- No:22179
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME... More Details >>
- No:22167
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Tolerance for overload (ME96SS series).
It is no influence on operating and characteristics even in the following cases. 1. Overcurrent 20 times of rated current is applied for 0.5 second. 2. Ov... More Details >>
- No:22159
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
About Low-voltage Power Distribution Products
It is possible to operate it by using two US-N* type. For the interlock ofboth US-N* type, UA-RE type reversible unit is used. More Details >>
- No:23375
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The consumption VA of a control circuit is 7VA for AC 100V product and14VA for AC 200 V product. More Details >>
- No:23348
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The minimum applicable load is as follows. Contact reliability is indicatedby fault rate λ60 (Number of fault / Operating cycles per one contact) atthe relia... More Details >>
- No:23320
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
These two different colors of the knob identify 2-element type and 3-element type of a thermal load relay. Gray: TH-* (Heater 2-element type)Orange: TH-*KP t... More Details >>
- No:23273
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
It is a standard equipment (automatic reset type) and 30ms of one-pulse is output at overload tripping. Hold-type circuit is necessary since the output time ... More Details >>
- No:22428
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Display upon upper/lower limit alarm (ME96SS series).
The measurement elements, including the digital indication, the unit indication and the phase indication, flash. And the “ALARM” indication and the “HI” in... More Details >>
- No:22169
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:36
- Category: Electrical Indicators
-
Power supply upon setting (ME96SS series).
It is necessary to supply an auxiliary power. As for an auxiliary power supply, you can use 50 Hz or 60 Hz from 100 VAC to 240 VAC and from 100 VDC to 240... More Details >>
- No:22161
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:14
- Category: Electrical Indicators
131-140 of Total 322