FAQ
FAQAbout Products
FAQ
Keyword Search
Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register addre... More Details >>
- No:22191
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Register address for active energy monitors in the MODBUS RTU communication (ME96SS series).
The acquired digit length of “1280”, “1281” and “1304” varies with the full load power. The acquired digit length of “1304” is 6-digit. Each of “1280” and... More Details >>
- No:22184
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:18
- Category: Electrical Indicators
-
Acquired values through MODBUS RTU.
The acquired value by communication should be multiplied by the multiplying factor to change into the measurement value. Please refer to Section 7.3 of ... More Details >>
- No:22183
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:13
- Category: Electrical Indicators
-
Communication failure with the upper system through MODBUS RTU.
Please check the following items. (A) Is the power supplied between MA and MB? (When the power is not supplied, the display does not work.) (B) Is the wir... More Details >>
- No:22182
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:08
- Category: Electrical Indicators
-
Measurement value different from other measuring instrument (ME96SS series).
In general, in case of measurement by the average method, the waveform including harmonics cause large error. This model uses the RMS value method and measu... More Details >>
- No:22177
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:54
- Category: Electrical Indicators
-
Disable an alarm for motor starting current (ME96SS series).
This model has “Motor Starting Current Mask Function”. This function stops the alarm output and updating of the maximum values during the setting time when a... More Details >>
- No:22175
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:51
- Category: Electrical Indicators
-
Measuring harmonics range (ME96SS series).
ME96SSHB-MB • Total harmonics and odd orders of harmonics from 1st to 31st •Effective value and distortion rate. • Harmonic current and Harmonic... More Details >>
- No:22173
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:46
- Category: Electrical Indicators
-
Checking non-displayed digit of active energy (ME96SS series).
Pressing buttons of the “+” and the “-” at the same time on the measurement screen for 2 seconds shifts the unit of active energy as follows. The measured ... More Details >>
- No:22172
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:44
- Category: Electrical Indicators
-
Display upon upper/lower limit alarm (ME96SS series).
The measurement elements, including the digital indication, the unit indication and the phase indication, flash. And the “ALARM” indication and the “HI” in... More Details >>
- No:22169
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:36
- Category: Electrical Indicators
-
Set values cannot be changed on the setting mode (ME96SS series).
When[SET] is flashing, the “Setting Value Confirmation Mode” is selected. In this case, the set values cannot be changed. Pressing the buttons of the “Set” ... More Details >>
- No:22168
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:22
- Category: Electrical Indicators