About Low-voltage Power Distribution ...
It is possible to replace it by user. More Details >>
About Low-voltage Power Distribution ...
It is possible to produce with the coil designation of less than AC 230V andDC 220V. Please add " SA" at the end of the type name. More Details >>
About Low-voltage Power Distribution ...
It can not be connected in parallel since the characteristics of each US-N/K/H type elements are differenct and the currents are unbalanced whenconnecting in... More Details >>
About Low-voltage Power Distribution ...
There is no polarity in the control coil. More Details >>
About Low-voltage Power Distribution ...
It is 1500V 50/60Hz between a terminal and a case for 1 min. More Details >>
About Low-voltage Power Distribution ...
This is because the delay time becomes shorter since the rebound force ofa spring against the suction force of a magnetic contactor increases if thecontact "... More Details >>
About Low-voltage Power Distribution ...
Time rating is 60sec and the rest time is for 2 hours. More Details >>
About Low-voltage Power Distribution ...
You need to connect the two terminal of No.15, 16 or 18 terminal to theload side of the contactor. (The remaining terminal is unnecessary toconnect.) More Details >>
About Low-voltage Power Distribution ...
DIN rail can be added to 5A frame and 8A frame of US-N* type asstandard and 20A frame as special product. Type name : US-N5SS(TE),US-N5SS(TE), US-N20(TE)RMMo... More Details >>
About Low-voltage Power Distribution ...
In the withstand voltage test, 2500V is applied for 1 min. The appliedlocation is as follows.1. Between the conductive part and the grounded metal part, and ... More Details >>
161-170 of Total 266