Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
About Low-voltage Power Distribution Products
It is the utilization category for opening/closing a heater load ofsemiconductor contactor specified in IEC60947-4-3. Utilization categoryAC-51 applies for "... More Details >>
- No:23318
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The withstand voltage of US-H type is 2.5kV. The applied location is asbelow.1. Between a main circuit terminal and a control circuit terminal2. Between all ... More Details >>
- No:23344
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
Since the control coil of DU-N type is AC operation DC excitation methodof an electromagnet type and it includes the surge suppresing function.Therefore, a s... More Details >>
- No:23353
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is not possible to produce an enclosed magnetic starter with a saturatedreactor. More Details >>
- No:23370
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
4-pole type in 100VAC or 110VAC
The rated operational voltages for them are 200 to 440VAC. If using them in 100VAC or 110VAC circuit, earth-leakage protection does not operate. More Details >>
- No:24820
- Release Date:2019/04/09 15:10
- Category: Earth Leakage Circuit Breakers
-
Set values cannot be changed on the setting mode (ME96SS series).
When[SET] is flashing, the “Setting Value Confirmation Mode” is selected. In this case, the set values cannot be changed. Pressing the buttons of the “Set” ... More Details >>
- No:22168
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:22
- Category: Electrical Indicators
-
Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
- Category: Electrical Indicators
-
Residual non-operating current
It is a current that does not leak-trip even if there is ground fault current or leakage current. In the standard, it is 50 % of the rated residual operating... More Details >>
- No:22356
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
How to select at Inverter circuit
Basically you have to consider the effect of harmonic waves, but there are two ways as below. 1. Refer to the recommended rated current by inverter manufactu... More Details >>
- No:22360
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It is a tripping zone which instantly trips, when significantly overcurrent such as short-circuit currents flow. More Details >>
- No:22363
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers