Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
Display digit of ACTIVE ENERGY
In the case of "6-digit display", the upper 3 digits of "9-digit display" are hidden. For details, refer to the Instrument User's Manual which you use. ・El... More Details >>
- No:24809
- Release Date:2019/03/27 14:44
- Category: Electrical Indicators
-
4-pole type in 100VAC or 110VAC
The rated operational voltages for them are 200 to 440VAC. If using them in 100VAC or 110VAC circuit, earth-leakage protection does not operate. More Details >>
- No:24820
- Release Date:2019/04/09 15:10
- Category: Earth Leakage Circuit Breakers
-
The power factor does not match the indication values through MODBUS.
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
- No:37807
- Release Date:2020/04/10 15:10
- Category: Electrical Indicators
-
Calorific value of the circuit breaker
1. The internal resistance (per pole) is described in the catalog and technical notes. 2. Power consumption (W) = RI^2 x Poles = Resistance (Ω) x Load curre... More Details >>
- No:38025
- Release Date:2021/01/22 17:39
- Category: Molded Case Circuit Breakers
-
Measurable minimum voltage (ME96SS series).
In case of the input voltage of less than 11 V, the measurement values are as follows: Voltage: 0 V,Power supply: 0 W, Reactive power: 0 var, Apparent pow... More Details >>
- No:22156
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:08
- Category: Electrical Indicators
-
Availability for changing set values while operating (ME96SS series).
It is no problem. The memorized data such as active energy, reactive energy, and apparent energy is not deleted. The measurement is continued during setti... More Details >>
- No:22164
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:19
- Category: Electrical Indicators
-
Replied value on the communication operation test of test mode (ME96SS series).
(A) Measurement values As for the measurement elements on the test mode screen, the set values are displayed. As for the other measurement elements, 0 is ... More Details >>
- No:22185
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:17
- Category: Electrical Indicators
-
Storage temperature range of MCCBs and ELCBs
It is from -25 to 55℃ in Trip or OFF position. However, it shall be in an environment without condensation and freezing even in a short time. More Details >>
- No:22426
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
About Low-voltage Power Distribution Products
It is the utilization category for opening/closing a motor load ofsemiconductor contactor specified in IEC60947-4-2. Utilization categoryAC-53a applies for "... More Details >>
- No:23345
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
Bar terminal material for 400A is aluminum alloy, and for 630A or higher is copper. More Details >>
- No:24819
- Release Date:2019/04/09 15:13
- Category: Molded Case Circuit Breakers