Recommended update period (ME96SS series).
The expected lifetime is 10 years. Is recommended to replace the device every 10 year. However the environment of installed location, such as temperature ... More Details >>
- No:22154
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:02
- Category: Electrical Indicators
-
How to connect to 2-pole breaker
(1) When "N" is marked on the breaker,connect the N phase wire as marked. (2) When "N" is not marked on the breaker, N phase wire can be connected to eith... More Details >>
- No:37700
- Release Date:2020/01/17 08:58
- Category: Molded Case Circuit Breakers
-
(1) and (2) are impossible. More Details >>
- No:24818
- Release Date:2019/04/09 15:03
- Category: Air Circuit Breakers
-
About Low-voltage Power Distribution Products
It is possible to open/close three-phase load by opening/closing two poleswith three-phase circuit. If US-H opens/closes two poles and theremaining pole is s... More Details >>
- No:23367
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is the utilization category for opening/closing a heater load ofsemiconductor contactor specified in IEC60947-4-3. Utilization categoryAC-51 applies for "... More Details >>
- No:23318
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is 1500V 50/60Hz between a terminal and a case for 1 min. More Details >>
- No:23310
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is a coil that opens/closes a magnetic contactor by magnetizing(applying suction force) or demagnetizing an electromagnet core. More Details >>
- No:23303
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
In the case of DC, since the load current breaking is more difficultcompared to AC, permanent magnet is provided at each main contactpoint and the arc is dri... More Details >>
- No:23289
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
If both of a closing coil and a tripping coil are continued to excite at thesame time, it will result in coil burnout. You need to design a system thatdoes n... More Details >>
- No:23282
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
There is no surge suppressor for a control coil. The control coil of S-T65 toS-N800 type has the AC operation DC excitation method and includes thesurge supp... More Details >>