FAQ


FAQAbout Products

FAQ
Keyword Search
Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
ACB General use Generator protection use
General protection relay (WS) of AE-SW type Air Circuit Breaker has tripping characteristic and function for general use. However, we also provide the replay... More Details >>
- No:22414
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
The test position is a position where a main circuit is in the "disconnected" state and only control circuit is in the "connected" state. Control circuit che... More Details >>
- No:22405
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Inverse time delay operating characteristic
It is a characteristic that operating time inversely become shorter as current increases. For Molded Case Circuit Breakers, protection characteristic meeting... More Details >>
- No:22387
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Fixed-type and Adjustable-type of V-type Operating handle
For Fixed type, the depth from the circuit breaker mounting surface to the panel board front is fixed. Adjustable-type is used when the depth from the circui... More Details >>
- No:22433
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
The applicable voltage is 440V or less. Moreover, High-speed type can be used from 85 to 484V, and Time-delay type can be used from 170 to 484V. More Details >>
- No:22421
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
- No:22401
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The push button is used for testing whether it definitely trips when an earth leakage current occurs. At this test, a Leakage Display button will be come out... More Details >>
- No:22347
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>
- No:22440
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
It is a button in order to mechanically trip a circuit breaker outside. It is used to confirm switching mechanism at the regular maintenance or sequence-chec... More Details >>
- No:22368
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It is an instantaneous tripping circuit breaker which does not have overcurrent tripping characteristic for standard circuit breaker and only protects agains... More Details >>
- No:22383
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
11-20 of Total 322