FAQ


FAQAbout Products
FAQ
Keyword Search
Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
About Low-voltage Power Distribution Products
It is not possible to replace it since we do not sell it as a unit. More Details >>
- No:23369
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The permissible variation range of frequency (short time variation) is ±5%. More Details >>
- No:23371
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is the peformance that open/close under the conditions specified in thestandard without energizing a main circuit. More Details >>
- No:23374
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
3P MCCB in 1-phase 2-wire circuit
It is possible. Refer to the figure for connection as below. More Details >>
- No:24811
- Release Date:2019/04/09 15:18
- Category: Molded Case Circuit Breakers
-
Horizontal allowable distance when installing ACB
Flatness of mounting plane: 1 mm or less.In addition, it is necessary to consider the horizontality of the panel. More Details >>
- No:37698
- Release Date:2020/01/17 17:32
- Category: Air Circuit Breakers
-
Setting change operation while power is on
It is forbidden to change the characteristic when the breaker ON. Over current trip and earth leakage trip characteristics should be changed by a person with... More Details >>
- No:37699
- Release Date:2020/01/18 09:58
- Category: Molded Case Circuit Breakers , Air Circuit Breakers
-
How to connect to 2-pole breaker
(1) When "N" is marked on the breaker,connect the N phase wire as marked. (2) When "N" is not marked on the breaker, N phase wire can be connected to eith... More Details >>
- No:37700
- Release Date:2020/01/17 08:58
- Category: Molded Case Circuit Breakers
-
Check the measurement values using MODBUS RTU communication
It is possible to check them using the Data Acquisition Software EMU4-SW1. It is available for download without payment from the following Web site. ... More Details >>
- No:37812
- Release Date:2020/04/10 15:10
- Category: Electrical Indicators
-
Type name of the operating handle
F-2SV is standard, F-2SVE is for emergency use. The difference is the color of the handle and its surroundings parts. More Details >>
- No:38028
- Release Date:2021/01/22 17:37
- Category: Accessories and Related Components
-
Measurable minimum load (ME96SS series).
In case of the input current of less than 0.005 A, the measurement values are as follows: Current: 0 A, Power supply: 0 W, Reactive power: 0 var, Apparent... More Details >>
- No:22155
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:04
- Category: Electrical Indicators
191-200 of Total 322