FAQ


FAQAbout Products
FAQ
Keyword Search
Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
About Low-voltage Power Distribution Products
It is a circuit flowing large current (several A to approximately 1000A)such as a motor and a lighting circuit, and a main contact (Betweenterminal number 1/... More Details >>
- No:23260
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is necessary to change the wires connected by solder to the board of theDL circuit since the wire length is short. Therefore, it is not possible toconnect... More Details >>
- No:23299
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
In the withstand voltage test, 2500V is applied for 1 min. The appliedlocation is as follows.1. Between the conductive part and the grounded metal part, and ... More Details >>
- No:23305
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
US-N* and US-H* type are compatible with IEC 60947-4-2(US-N* type)and IEC 60947-4-3(US-N/H type). US-N* type is also compatible withUL, TUV, EC and CCC. More Details >>
- No:23349
- Release Date:2018/09/12 15:12
- Update:2021/04/14 09:57
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is a product that can control two main circuit elements independently,and can be downsized when two or more single-pole type SSCs are used.It is also effe... More Details >>
- No:23376
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
4-pole type in 100VAC or 110VAC
The rated operational voltages for them are 200 to 440VAC. If using them in 100VAC or 110VAC circuit, earth-leakage protection does not operate. More Details >>
- No:24820
- Release Date:2019/04/09 15:10
- Category: Earth Leakage Circuit Breakers
-
Availability for direct measurement of 400V loads (ME96SS series).
This model is available for direct measurement of 400V loads at the STAR connection in Three-phase 3-wire system. More Details >>
- No:22150
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Tolerance for overload (ME96SS series).
It is no influence on operating and characteristics even in the following cases. 1. Overcurrent 20 times of rated current is applied for 0.5 second. 2. Ov... More Details >>
- No:22159
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Rating of a circuit breaker for transformers primary protection
When making a transformer to energize, a large inrush current may flow. The circuit breaker is therefore required to prevent unwanted trip. The selection of ... More Details >>
- No:22343
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It is voltage which ensures withstand voltage and it is used as basis to determine insulation distance. More Details >>
- No:22362
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
211-220 of Total 322