How to install cassette type accessories
A circuit breaker shall be Trip position when installing Cassette type accessory. The breaker may be damaged if installing in "ON" or "OFF" position. Moreove... More Details >>
- No:22422
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register addre... More Details >>
- No:22191
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
- Category: Electrical Indicators
-
About Low-voltage Power Distribution Products
The main part of SRT(D)-NF type is a special product and different fromthe standard product relay (SR(D)-N type). Therefore, we do not providethe timer unit ... More Details >>
- No:23264
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It stops a motor rapidly by reversing connetion of a contact. More Details >>
- No:23262
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The temparature rise of a terminal connected by customer is designed tobe under 65℃ according to the standard. For our products, there is nospecification abo... More Details >>
- No:23259
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
When installing a thermal load relay in the delta phase and detectingphase current, you select a heater designation that can be set to 1 / √ 3times of the mo... More Details >>
- No:23240
- Release Date:2018/09/12 15:11
- Category: Motor Starters
-
Default setting of electronic breakers
Each setting knob of the overcurrent trip characteristic is set to the maximum value and then shipped if not specified. However, only the pre-alarm is set to... More Details >>
- No:22438
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The power factor does not match the indication values through MODBUS.
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
- No:37807
- Release Date:2020/04/10 15:10
- Category: Electrical Indicators
-
MCCB, ELCB and ACB at higher altitudes
In that case, the rated current and the rated voltage shall be reduced. Refer to the table of derating factors as below. More Details >>
- No:24801
- Release Date:2019/04/09 15:17
- Category: Molded Case Circuit Breakers