FAQ


FAQAbout Products

FAQ
Keyword Search
Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
About Low-voltage Power Distribution Products
The withstand voltage of US-N5SS, US-N8SS, US-N70NS and US-N80NStype is 2kV. The withstand voltage of US-N20 to 50 type is 2.5kV. Theapplied points are as fo... More Details >>
- No:23351
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
We do not provide it. More Details >>
- No:23350
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The consumption VA of a control circuit is 7VA for AC 100V product and14VA for AC 200 V product. More Details >>
- No:23348
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
We have a transparent protective cover of live part for US-H20(DD) to US-H50(DD) that can be installed easily as an optional part. The type nameis UN-CV501US. More Details >>
- No:23347
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The maximum ambient temparature for US-N/K/H type is 60℃ and theycan not be used with more than 60℃. If the temparature is more than60℃, you need to consider... More Details >>
- No:23346
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is the utilization category for opening/closing a motor load ofsemiconductor contactor specified in IEC60947-4-2. Utilization categoryAC-53a applies for "... More Details >>
- No:23345
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The withstand voltage of US-H type is 2.5kV. The applied location is asbelow.1. Between a main circuit terminal and a control circuit terminal2. Between all ... More Details >>
- No:23344
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is time from magnetizing or demagnetizing a control coil to operatingcontact (turning contact "ON" or "OFF"). More Details >>
- No:23343
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
It is not possible to change a contact of SD-Q type. More Details >>
- No:23341
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
The Earth Leakaga Circuit Breaker does not work since leakage current ofSSC is the current flowing from the main circuit element to the load sidewhen opening. More Details >>
- No:23338
- Release Date:2018/09/12 15:12
- Category: Motor Starters
261-270 of Total 323