Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
- Category: Electrical Indicators
-
AL (Alarm switch) is a switch which electrically displays tripping state of a circuit breaker.The markings of the switch are 8/ALa, 96/ALb and 95/ALc.*When t... More Details >>
- No:22350
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It is voltage which ensures withstand voltage and it is used as basis to determine insulation distance. More Details >>
- No:22362
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It is a tripping zone which instantly trips, when significantly overcurrent such as short-circuit currents flow. More Details >>
- No:22363
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
It is an instantaneous tripping circuit breaker which does not have overcurrent tripping characteristic for standard circuit breaker and only protects agains... More Details >>
- No:22383
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
Inst tripping current value of AC/DC common breaker
At time-delay tripping zone, it operates with bimetal, therefore the characteristics of AC and DC should be same if the effective values of them are same. Ho... More Details >>
- No:22392
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AL/AX/SHT/UVT terminal markings and wire colors
The color of terminal identification tube and lead wire is same.For one AL switch, 98/ALa terminal : red, 96/ALb terminal : blue, 95/ALc terminal : grayFor S... More Details >>
- No:22396
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>
- No:22418
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
ACB add earth leakage protection
When earth leakage current protection module (ER) is attached, it is possible to protect against earth leakage current. "Trip" or "Alarm signal output" can b... More Details >>
- No:22420
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
For ACB, Line and Load are not defined on the main circuit terminals. Reverse connection is available without any limitation. More Details >>
- No:22425
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers