A shunt trip (SHT) is an internal accessory which electrically and remotely trips a circuit breaker. When the supply voltage of the SHT is remained between 7... More Details >>
F-type and V-type operating handle
Both of F-type and V-type can remotely operate a circuit breaker in the panel board and the design of 800A fame or less are unified. Features are as follows.... More Details >>
ELCB Default setting Time-delay type ...
Both of the adjustment knob is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage Circuit Breaker ... More Details >>
ACB General use Generator protection...
General protection relay (WS) of AE-SW type Air Circuit Breaker has tripping characteristic and function for general use. However, we also provide the replay... More Details >>
It is possible to use it if you connect with right and left poles, not neutral pole. Since electronic circuit power supply for earth leakage detection is tak... More Details >>
Residual non-operating current
It is a current that does not leak-trip even if there is ground fault current or leakage current. In the standard, it is 50 % of the rated residual operating... More Details >>
About Low-voltage Power Distribution ...
We do not provide it. More Details >>
Earth leakage protective coordination
Since the total electric circuit length of upstream circuit breaker side is longer than that of downstream circuit breaker, constant earth leakage current b... More Details >>
About Low-voltage Power Distribution ...
The maximum ambient temparature for US-N/K/H type is 60℃ and theycan not be used with more than 60℃. If the temparature is more than60℃, you need to consider... More Details >>
About Low-voltage Power Distribution ...
The head-on type of UN-AX 2 and AX 4 type can be installed. The side-onunit of UN-AX 11 type can not be installed. More Details >>