Release element in neutral (4P breaker)
AE-SW 4-poles with WS relay (general protection) has overcurrent protection for neutral-pole. The tripping characteristic is same as phase-pole. Moreover, A... More Details >>
- No:22441
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Default setting of electronic breakers
Each setting knob of the overcurrent trip characteristic is set to the maximum value and then shipped if not specified. However, only the pre-alarm is set to... More Details >>
- No:22438
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The applicable voltage is 440V or less. Moreover, High-speed type can be used from 85 to 484V, and Time-delay type can be used from 170 to 484V. More Details >>
- No:22421
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
When Power-Fuse (PF) is used as a high-voltage side protection device, coordination with MCCBs on the secondary side shall be achieved. Therefore, MCCB has l... More Details >>
- No:22403
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
It is possible to modify to Rear-connection type by Mitsubishi's certified staff. More Details >>
- No:22399
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
AL (Alarm switch) is a switch which electrically displays tripping state of a circuit breaker.The markings of the switch are 8/ALa, 96/ALb and 95/ALc.*When t... More Details >>
- No:22350
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
We don't provide the earth leakage circuit beaker for PV power. Please use a general leakage circuit breaker. However, you need to select a reverse-connectab... More Details >>
- No:22348
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
Regardless of setting, the value of the default digit length is replied. When the register address “1304” for 6-digit display is set, the value varies w... More Details >>
- No:22189
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:26
- Category: Electrical Indicators
-
Concurrent-use of MODBUS RTU and MODBUS TCP (ME96SS series).
MODBUS RTU communication and MODBUS TCP communication can be used at the same time. More Details >>
- No:22188
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Acquired values through MODBUS RTU.
The acquired value by communication should be multiplied by the multiplying factor to change into the measurement value. Please refer to Section 7.3 of ... More Details >>