Error in the measurement value (ME96SS series).
There is a possibility of the wiring error for VT/CT to this model. Please check the wiring for VT/CT and this model. More Details >>
- No:22179
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
About Low-voltage Power Distribution Products
The consumption VA of UA-DR1 type are 200V*0.03A=6VA for AC200Vproduct and 100V*0.03A=3VA for AC100V product. More Details >>
- No:23368
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
About Low-voltage Power Distribution Products
When carrying the rated current at ambient temperature of 40℃, themaximum temparature of cooling fin is approximately 90℃. More Details >>
- No:23360
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
Replied value on the communication operation test of test mode (ME96SS series).
(A) Measurement values As for the measurement elements on the test mode screen, the set values are displayed. As for the other measurement elements, 0 is ... More Details >>
- No:22185
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:17
- Category: Electrical Indicators
-
Connectable number of MODBUS RTU (ME96SS series).
It is connectable with up to 31 units. It is necessary to prepare at least 3 PCs for connecting with 64 units. (31 units + 31 units + 2 units) More Details >>
- No:22190
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
About Low-voltage Power Distribution Products
When carrying the rated current at ambient temperature of 40℃ (whencarrying the rated heater load), the maximum temparature of cooling finis approximately 100℃. More Details >>
- No:23358
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
Calorific value of the circuit breaker
1. The internal resistance (per pole) is described in the catalog and technical notes. 2. Power consumption (W) = RI^2 x Poles = Resistance (Ω) x Load curre... More Details >>
- No:38025
- Release Date:2021/01/22 17:39
- Category: Molded Case Circuit Breakers
-
Type name of the operating handle
F-2SV is standard, F-2SVE is for emergency use. The difference is the color of the handle and its surroundings parts. More Details >>
- No:38028
- Release Date:2021/01/22 17:37
- Category: Accessories and Related Components
-
The power factor does not match the indication values through MODBUS.
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
- No:37807
- Release Date:2020/04/10 15:10
- Category: Electrical Indicators
-
Read data stored by the built-in logging function
The stored data can be read from MODBUS RTU communication. To use this function, MODBUS RTU communication is required. It is not available with MOD... More Details >>
- No:37808
- Release Date:2020/04/10 15:09
- Category: Electrical Indicators