FAQ


FAQAbout Products
FAQ
Keyword Search
Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
AX (Auxiliary switch) is a switch which electrically displays the ON / OFF state. The markings are 14/AXa, 12/AXb and 11/AXc.* If the circuit breaker itself ... More Details >>
- No:22354
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
About Low-voltage Power Distribution Products
It is possible to operate it by using two US-N* type. For the interlock ofboth US-N* type, UA-RE type reversible unit is used. More Details >>
- No:23375
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
For Shunt Trip (SHT), it is the time from voltage application to open ACB main contact * AE3200-SW or less, AE4000-SWA: 0.04 sec or less* AE4000-SW to AE6300... More Details >>
- No:22418
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
ELCB Default setting Time-delay type sensitivity
Both of the adjustment knob is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage Circuit Breaker ... More Details >>
- No:22388
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Display upon upper/lower limit alarm (ME96SS series).
The measurement elements, including the digital indication, the unit indication and the phase indication, flash. And the “ALARM” indication and the “HI” in... More Details >>
- No:22169
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:36
- Category: Electrical Indicators
-
The operating/storage temperature and humidity
Storage temperature range: -25 °C to +75 °C Operating temperature range: -5 °C to +55 °C (Average: 35 °C or lower) Operating humidity range: 0% to 85% an... More Details >>
- No:22153
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:56
- Category: Electrical Indicators
-
The number of trip durability by using SHT and UVT is 10% of the opening/closing number including the number of trips by overcurrent, trip button and test bu... More Details >>
- No:22407
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Disable an alarm for motor starting current (ME96SS series).
This model has “Motor Starting Current Mask Function”. This function stops the alarm output and updating of the maximum values during the setting time when a... More Details >>
- No:22175
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:51
- Category: Electrical Indicators
-
(1) and (2) are impossible. More Details >>
- No:24818
- Release Date:2019/04/09 15:03
- Category: Air Circuit Breakers
-
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
- No:22401
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
31-40 of Total 322