Wiring for only measuring current (ME96SS series).
It is unnecessary. (It is necessary to prepare an auxiliary power supply which supplies power between MA and MB.) More Details >>
- No:22174
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:50
- Category: Electrical Indicators
-
It is a button in order to trip MCCB. It is used for regular inspection of the switching mechanism, and trip condition of MCCB when Alarm switch (AL) and Shu... More Details >>
- No:22444
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
The time between application of voltage to the closing coil (CC) and closing of the main contact is 0.08 sec or less. More Details >>
- No:22440
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Fixed-type and Adjustable-type of V-type Operating handle
For Fixed type, the depth from the circuit breaker mounting surface to the panel board front is fixed. Adjustable-type is used when the depth from the circui... More Details >>
- No:22433
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
The operating handle is an external accessory for a circuit breaker and there is no safety standard for the operating handle itself. Therefore, there is no C... More Details >>
- No:22408
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It is an instantaneous tripping circuit breaker which does not have overcurrent tripping characteristic for standard circuit breaker and only protects agains... More Details >>
- No:22383
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
Horizontal allowable distance when installing ACB
Flatness of mounting plane: 1 mm or less.In addition, it is necessary to consider the horizontality of the panel. More Details >>
- No:37698
- Release Date:2020/01/17 17:32
- Category: Air Circuit Breakers
-
MCB can be used at 85% or less relative humidity and no condensation. More Details >>
- No:24822
- Release Date:2019/04/09 15:11
- Category: Miniature Circuit Breakers
-
Generally, there is no Mechanical Trip indication of continuous output for AE-SW. It is necessary to indicate electrically by using OCR Alarm (AL) output or ... More Details >>
- No:22432
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Insulating barrier in the package
Use the insulation barrier if they are packed with. If not using that, breaking performance is not guaranteed. For models that the insulation barrier is not ... More Details >>
- No:22406
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components