Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
When the AC waveform distorted due to harmonics, the value changes. (For AC without harmonics, the calculated value will match with the displayed value.) A... More Details >>
- No:22178
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:56
- Category: Electrical Indicators
-
Measurement value different from other measuring instrument (ME96SS series).
In general, in case of measurement by the average method, the waveform including harmonics cause large error. This model uses the RMS value method and measu... More Details >>
- No:22177
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:54
- Category: Electrical Indicators
-
Set values cannot be changed on the setting mode (ME96SS series).
When[SET] is flashing, the “Setting Value Confirmation Mode” is selected. In this case, the set values cannot be changed. Pressing the buttons of the “Set” ... More Details >>
- No:22168
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:22
- Category: Electrical Indicators
-
About Low-voltage Power Distribution Products
It is the utilization category for opening/closing a motor load ofsemiconductor contactor specified in IEC60947-4-2. Utilization categoryAC-53a applies for "... More Details >>
- No:23345
- Release Date:2018/09/12 15:12
- Category: Motor Starters
-
This contact(SBC) is used to auxiliary switch(AXb) contact. When Drawout type ACB is moved from "test" position to "disconnect" position, AXb contact will b... More Details >>
- No:22416
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
-
Inst tripping current value of AC/DC common breaker
At time-delay tripping zone, it operates with bimetal, therefore the characteristics of AC and DC should be same if the effective values of them are same. Ho... More Details >>
- No:22392
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
ELCB Default setting Time-delay type sensitivity
Both of the adjustment knob is set to the maximum value when shipping in order to prevent unwanted earth leakage tripping when Earth Leakage Circuit Breaker ... More Details >>
- No:22388
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
Setting for communication (ME96SS series).
1) For the main body of ME96: Please set the following values on the “Set-up menu 2”. In case of MODBUS RTU Set-up menu No. Setti... More Details >>
- No:22181
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:05
- Category: Electrical Indicators
-
Power supply upon setting (ME96SS series).
It is necessary to supply an auxiliary power. As for an auxiliary power supply, you can use 50 Hz or 60 Hz from 100 VAC to 240 VAC and from 100 VDC to 240... More Details >>
- No:22161
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:14
- Category: Electrical Indicators
-
Release element in neutral (4P breaker)
AE-SW 4-poles with WS relay (general protection) has overcurrent protection for neutral-pole. The tripping characteristic is same as phase-pole. Moreover, A... More Details >>
- No:22441
- Release Date:2018/08/31 14:33
- Category: Air Circuit Breakers
61-70 of Total 322