Low-voltage Power Distribution Products
FAQ within [ Low-voltage Power Distribution Products ]
-
It is the number that can be opened/closed per hour under the conditions specified in the standard. More Details >>
- No:22436
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Almost ELCBs can be connected n reverse. Check the item column of specification table "reverse connection (below 230 V AC)" in the catalog. If it says "Possi... More Details >>
- No:22434
- Release Date:2018/08/31 14:33
- Category: Earth Leakage Circuit Breakers
-
CP30-BA AL and AX switch micro-load can be provided. And the number of installation is same as standard AL and AX switch. However, if multiple AL and AX are ... More Details >>
- No:22427
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Equipment
-
The number of trip durability by using SHT and UVT is 10% of the opening/closing number including the number of trips by overcurrent, trip button and test bu... More Details >>
- No:22407
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
Use with 24V, 0.5A or more for AC and DC in normal use. If the breakers are used less than 24V, use with 6V, 1A or more. Moreover, regular inspection of is ... More Details >>
- No:22401
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
All our products are compliant with CCC (China Compulsory Certification). More Details >>
- No:22386
- Release Date:2018/08/31 14:33
- Category: Circuit Breakers for Use in Particular Applications
-
No, you must not use 2-pole circuit breaker as 1-pole circuit breaker (series connection as only single phase ). If using it as 1-pole circuit breaker, these... More Details >>
- No:22382
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Pre-Alarm is a function which outputs an alarm if the load current exceeds setting current value. This is useful for securing continuous power supply and pre... More Details >>
- No:22376
- Release Date:2018/08/31 14:33
- Category: Accessories and Related Components
-
It means a space between the edge of a exhaust port and panel component ( such as wall or duct) of a circuit breaker. The arc space is needed for smoothly di... More Details >>
- No:22373
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers
-
Operating ambient temperature is set to - 10℃ to 40℃. ( However, its average over a period of 24h does not exceed 35℃.) In the case that the ambient temperat... More Details >>
- No:22370
- Release Date:2018/08/31 14:33
- Category: Molded Case Circuit Breakers