FAQ
FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Power Management Meters
FAQ
Keyword Search
Power Management Meters
FAQ within [ Power Management Meters ]
-
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register addre... More Details >>
- No:22191
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Sample program for CC-LINK communication (ME96SS series)
Sample programs are described in Programming Manual. Please refer to suitable programming manual depending on CC-Link version which you use. ・Programming M... More Details >>
- No:24804
- Release Date:2019/03/27 12:12
- Category: Electrical Indicators
-
Check the measurement values using MODBUS RTU communication
It is possible to check them using the Data Acquisition Software EMU4-SW1. It is available for download without payment from the following Web site. ... More Details >>
- No:37812
- Release Date:2020/04/10 15:10
- Category: Electrical Indicators
-
Availability for special primary current and special primary voltage (ME96SS series).
This model is able to be used under unusual primary current and unusual primary voltage as long as the user sets each value within the selectable range as ... More Details >>
- No:22148
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:15
- Category: Electrical Indicators
-
Response speed of the analog output (ME96SS series).
The response speed of the analog output is 2 seconds or less. The response speed of harmonic measurement is 10 seconds or less. More Details >>
- No:22157
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:12
- Category: Electrical Indicators
-
IP protection class (ME96SS series).
In a board installation state, the protection class is equivalent to IP50. This model is not waterproof. More Details >>
- No:22158
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:13
- Category: Electrical Indicators
-
Installation compatibility with ME96NSR (ME96SS series).
They are the same dimensions. (Dimensions of an installation hole is 92 mm in length and width. Install this model two points with mounting brackets.) More Details >>
- No:22160
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Wiring for only measuring current (ME96SS series).
It is unnecessary. (It is necessary to prepare an auxiliary power supply which supplies power between MA and MB.) More Details >>
- No:22174
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:50
- Category: Electrical Indicators
-
Error in the measurement value (ME96SS series).
There is a possibility of the wiring error for VT/CT to this model. Please check the wiring for VT/CT and this model. More Details >>
- No:22179
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
The power factor does not match the indication values through MODBUS.
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
- No:37807
- Release Date:2020/04/10 15:10
- Category: Electrical Indicators
21-30 of Total 57