- FAQ > Low-voltage Power Distribution Products > Power Management Meters
FAQ
Keyword Search
Power Management Meters
FAQ within [ Power Management Meters ]
-
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register addre... More Details >>
- No:22191
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Concurrent-use of MODBUS RTU and MODBUS TCP (ME96SS series).
MODBUS RTU communication and MODBUS TCP communication can be used at the same time. More Details >>
- No:22188
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Setting for communication (ME96SS series).
1) For the main body of ME96: Please set the following values on the “Set-up menu 2”. In case of MODBUS RTU Set-up menu No. Setti... More Details >>
- No:22181
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:05
- Category: Electrical Indicators
-
Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
- Category: Electrical Indicators
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME... More Details >>
- No:22167
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Availability for changing set values while operating (ME96SS series).
It is no problem. The memorized data such as active energy, reactive energy, and apparent energy is not deleted. The measurement is continued during setti... More Details >>
- No:22164
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:19
- Category: Electrical Indicators
-
Compensation for power failure (ME96SS series).
The setting data are memorized in nonvolatile memory, so the data is not deleted at the time of a power interruption. (The main body does not use a battery.)... More Details >>
- No:22163
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:16
- Category: Electrical Indicators
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME9... More Details >>
- No:22162
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Power supply upon setting (ME96SS series).
It is necessary to supply an auxiliary power. As for an auxiliary power supply, you can use 50 Hz or 60 Hz from 100 VAC to 240 VAC and from 100 VDC to 240... More Details >>
- No:22161
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:14
- Category: Electrical Indicators
-
Tolerance for overload (ME96SS series).
It is no influence on operating and characteristics even in the following cases. 1. Overcurrent 20 times of rated current is applied for 0.5 second. 2. Ov... More Details >>
- No:22159
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators