Compensation for power failure (ME96SS series).
The setting data are memorized in nonvolatile memory, so the data is not deleted at the time of a power interruption. (The main body does not use a battery.)... More Details >>
- No:22163
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:16
- Category: Electrical Indicators
-
Setting for communication (ME96SS series).
1) For the main body of ME96: Please set the following values on the “Set-up menu 2”. In case of MODBUS RTU Set-up menu No. Setti... More Details >>
- No:22181
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:05
- Category: Electrical Indicators
-
Register address for active energy monitors in the MODBUS RTU communication (ME96SS series).
The acquired digit length of “1280”, “1281” and “1304” varies with the full load power. The acquired digit length of “1304” is 6-digit. Each of “1280” and... More Details >>
- No:22184
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:18
- Category: Electrical Indicators
-
Concurrent-use of MODBUS RTU and CC-Link.
MODBUS RTU communication and CC-Link communication can be used at the same time. More Details >>
- No:22187
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME9... More Details >>
- No:22162
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
- Category: Electrical Indicators
-
Measuring harmonics range (ME96SS series).
ME96SSHB-MB • Total harmonics and odd orders of harmonics from 1st to 31st •Effective value and distortion rate. • Harmonic current and Harmonic... More Details >>
- No:22173
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:46
- Category: Electrical Indicators
-
Accuracy class index of active energy
Accuracy class index of active energy is a number which gives the limits of the permissible percentage error as defined in the IEC62053-22. More Details >>
- No:37704
- Release Date:2020/01/29 18:36
- Category: Electrical Indicators
-
The power factor does not match the indication values through MODBUS.
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
- No:37807
- Release Date:2020/04/10 15:10
- Category: Electrical Indicators
-
Response speed of the analog output (ME96SS series).
The response speed of the analog output is 2 seconds or less. The response speed of harmonic measurement is 10 seconds or less. More Details >>
- No:22157
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:12
- Category: Electrical Indicators