Communication failure with the upper system through MODBUS RTU.
Please check the following items. (A) Is the power supplied between MA and MB? (When the power is not supplied, the display does not work.) (B) Is the wir... More Details >>
- No:22182
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:08
- Category: Electrical Indicators
-
Register address for active energy monitors in the MODBUS RTU communication (ME96SS series).
The acquired digit length of “1280”, “1281” and “1304” varies with the full load power. The acquired digit length of “1304” is 6-digit. Each of “1280” and... More Details >>
- No:22184
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:18
- Category: Electrical Indicators
-
The power factor does not match the indication values through MODBUS.
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
- No:37807
- Release Date:2020/04/10 15:10
- Category: Electrical Indicators
-
Measuring harmonics range (ME96SS series).
ME96SSHB-MB • Total harmonics and odd orders of harmonics from 1st to 31st •Effective value and distortion rate. • Harmonic current and Harmonic... More Details >>
- No:22173
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:46
- Category: Electrical Indicators
-
Measurable minimum voltage (ME96SS series).
In case of the input voltage of less than 11 V, the measurement values are as follows: Voltage: 0 V,Power supply: 0 W, Reactive power: 0 var, Apparent pow... More Details >>
- No:22156
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:08
- Category: Electrical Indicators
-
Availability for changing set values while operating (ME96SS series).
It is no problem. The memorized data such as active energy, reactive energy, and apparent energy is not deleted. The measurement is continued during setti... More Details >>
- No:22164
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:19
- Category: Electrical Indicators
-
Wiring for only measuring current (ME96SS series).
It is unnecessary. (It is necessary to prepare an auxiliary power supply which supplies power between MA and MB.) More Details >>
- No:22174
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:50
- Category: Electrical Indicators
-
Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
- Category: Electrical Indicators
-
Disable an alarm for motor starting current (ME96SS series).
This model has “Motor Starting Current Mask Function”. This function stops the alarm output and updating of the maximum values during the setting time when a... More Details >>
- No:22175
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:51
- Category: Electrical Indicators
-
Error in the measurement value (ME96SS series).
There is a possibility of the wiring error for VT/CT to this model. Please check the wiring for VT/CT and this model. More Details >>
- No:22179
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
31-40 of Total 57