Wiring for only measuring current (ME96SS series).
It is unnecessary. (It is necessary to prepare an auxiliary power supply which supplies power between MA and MB.) More Details >>
- No:22174
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:50
- Category: Electrical Indicators
-
Operation at the reversed phase connection (ME96SS series).
This model operates normally even at the reversed phase sequence. It is unnecessary to change wiring. More Details >>
- No:22170
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:41
- Category: Electrical Indicators
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME... More Details >>
- No:22167
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Compensation for power failure (ME96SS series).
The setting data are memorized in nonvolatile memory, so the data is not deleted at the time of a power interruption. (The main body does not use a battery.)... More Details >>
- No:22163
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:16
- Category: Electrical Indicators
-
Measurable minimum voltage (ME96SS series).
In case of the input voltage of less than 11 V, the measurement values are as follows: Voltage: 0 V,Power supply: 0 W, Reactive power: 0 var, Apparent pow... More Details >>
- No:22156
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:08
- Category: Electrical Indicators
-
Display digit of ACTIVE ENERGY
In the case of "6-digit display", the upper 3 digits of "9-digit display" are hidden. For details, refer to the Instrument User's Manual which you use. ・El... More Details >>
- No:24809
- Release Date:2019/03/27 14:44
- Category: Electrical Indicators
-
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register addre... More Details >>
- No:22191
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Availability for special primary current and special primary voltage (ME96SS series).
This model is able to be used under unusual primary current and unusual primary voltage as long as the user sets each value within the selectable range as ... More Details >>
- No:22148
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:15
- Category: Electrical Indicators
-
Standards for this model (ME96SS series).
This model is compliant with CE marking, UL standard, KC Mark and FCC/IC. More Details >>
- No:22146
- Release Date:2018/08/27 16:41
- Update:2020/04/10 14:27
- Category: Electrical Indicators
-
The power factor does not match the indication values through MODBUS.
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
- No:37807
- Release Date:2020/04/10 15:10
- Category: Electrical Indicators