FAQ


FAQAbout Products
- FAQ > Low-voltage Power Distribution Products > Power Management Meters
FAQ
Keyword Search
Power Management Meters
FAQ within [ Power Management Meters ]
-
Acquired values through MODBUS RTU.
The acquired value by communication should be multiplied by the multiplying factor to change into the measurement value. Please refer to Section 7.3 of ... More Details >>
- No:22183
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:13
- Category: Electrical Indicators
-
IP protection class (ME96SS series).
In a board installation state, the protection class is equivalent to IP50. This model is not waterproof. More Details >>
- No:22158
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:13
- Category: Electrical Indicators
-
Connectable number of MODBUS RTU (ME96SS series).
It is connectable with up to 31 units. It is necessary to prepare at least 3 PCs for connecting with 64 units. (31 units + 31 units + 2 units) More Details >>
- No:22190
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Support status for IEC61850 (ME96SS series).
This model does NOT comply with the IEC61850. More Details >>
- No:22147
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:11
- Category: Electrical Indicators
-
Measurable minimum load (ME96SS series).
In case of the input current of less than 0.005 A, the measurement values are as follows: Current: 0 A, Power supply: 0 W, Reactive power: 0 var, Apparent... More Details >>
- No:22155
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:04
- Category: Electrical Indicators
-
Sample program for MODBUS RTU communication (ME96SS series)
Sample programs are described in Programming Manual. Please refer to MODBUS Interface specifications(LSPM-0075) The programming manual can be downloaded fr... More Details >>
- No:24805
- Release Date:2019/03/27 12:12
- Category: Electrical Indicators
-
Communication failure with the upper system through MODBUS RTU.
Please check the following items. (A) Is the power supplied between MA and MB? (When the power is not supplied, the display does not work.) (B) Is the wir... More Details >>
- No:22182
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:08
- Category: Electrical Indicators
-
Validation method for communication function (ME96SS series).
This model has the test function of the communication operation. For detail, refer to User's Manual: Detailed Edition for setting. More Details >>
- No:22180
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
The operating/storage temperature and humidity
Storage temperature range: -25 °C to +75 °C Operating temperature range: -5 °C to +55 °C (Average: 35 °C or lower) Operating humidity range: 0% to 85% an... More Details >>
- No:22153
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:56
- Category: Electrical Indicators
-
Tolerance for overload (ME96SS series).
It is no influence on operating and characteristics even in the following cases. 1. Overcurrent 20 times of rated current is applied for 0.5 second. 2. Ov... More Details >>
- No:22159
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
41-50 of Total 57