Power Management Meters
FAQ within [ Power Management Meters ]
-
Compensation for power failure (ME96SS series).
The setting data are memorized in nonvolatile memory, so the data is not deleted at the time of a power interruption. (The main body does not use a battery.)... More Details >>
- No:22163
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:16
- Category: Electrical Indicators
-
Power supply upon setting (ME96SS series).
It is necessary to supply an auxiliary power. As for an auxiliary power supply, you can use 50 Hz or 60 Hz from 100 VAC to 240 VAC and from 100 VDC to 240... More Details >>
- No:22161
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:14
- Category: Electrical Indicators
-
Availability for battery exchange for Logging Unit (ME96SS series).
The battery of the Logging unit (ME-0000BU-SS96) is NOT exchangeable. Please order a new unit. More Details >>
- No:22152
- Release Date:2018/08/27 16:41
- Update:2020/04/10 15:54
- Category: Electrical Indicators
-
Sample program for MODBUS RTU communication (ME96SS series)
Sample programs are described in Programming Manual. Please refer to MODBUS Interface specifications(LSPM-0075) The programming manual can be downloaded fr... More Details >>
- No:24805
- Release Date:2019/03/27 12:12
- Category: Electrical Indicators
-
Concurrent-use of MODBUS RTU and CC-Link.
MODBUS RTU communication and CC-Link communication can be used at the same time. More Details >>
- No:22187
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Installation compatibility with ME96NSR (ME96SS series).
They are the same dimensions. (Dimensions of an installation hole is 92 mm in length and width. Install this model two points with mounting brackets.) More Details >>
- No:22160
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
-
Wiring for only measuring current (ME96SS series).
It is unnecessary. (It is necessary to prepare an auxiliary power supply which supplies power between MA and MB.) More Details >>
- No:22174
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:50
- Category: Electrical Indicators
-
Measurement value different from other measuring instrument (ME96SS series).
In general, in case of measurement by the average method, the waveform including harmonics cause large error. This model uses the RMS value method and measu... More Details >>
- No:22177
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:54
- Category: Electrical Indicators
-
Replied value on the communication operation test of test mode (ME96SS series).
(A) Measurement values As for the measurement elements on the test mode screen, the set values are displayed. As for the other measurement elements, 0 is ... More Details >>
- No:22185
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:17
- Category: Electrical Indicators
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME9... More Details >>
- No:22162
- Release Date:2018/08/27 16:41
- Category: Electrical Indicators
1-10 of Total 57