FAQ


FAQAbout Products

- FAQ > Low-voltage Power Distribution Products > Power Management Meters > Electrical Indicators
FAQ
Keyword Search
FAQ within [ Electrical Indicators ]
-
Availability of an option for ME96NS Series (ME96SS series).
An option for ME96NS series can NOT be installed to the main body of ME96SS series. An option for ME96SS series can NOT be installed to the main body of ME9... More Details >>
- No:22162
- Release Date:2018/08/27 16:41
-
Display upon upper/lower limit alarm (ME96SS series).
The measurement elements, including the digital indication, the unit indication and the phase indication, flash. And the “ALARM” indication and the “HI” in... More Details >>
- No:22169
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:36
-
The power factor does not match the indication values through MODBUS.
Please check the register addresses. The register address for the present value of the power factor of each phase is “0789”. There are the register... More Details >>
- No:37807
- Release Date:2020/04/10 15:10
-
Availability for direct measurement of 400V loads (ME96SS series).
This model is available for direct measurement of 400V loads at the STAR connection in Three-phase 3-wire system. More Details >>
- No:22150
- Release Date:2018/08/27 16:41
-
Checking non-displayed digit of active energy (ME96SS series).
Pressing buttons of the “+” and the “-” at the same time on the measurement screen for 2 seconds shifts the unit of active energy as follows. The measured ... More Details >>
- No:22172
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:44
-
Connectable number of MODBUS RTU (ME96SS series).
It is connectable with up to 31 units. It is necessary to prepare at least 3 PCs for connecting with 64 units. (31 units + 31 units + 2 units) More Details >>
- No:22190
- Release Date:2018/08/27 16:41
-
With ME96SS ver.B, four measurement values can be checked digitally on one screen. For models before ME96SS ver.B, up to three measured values can be checked... More Details >>
- No:37806
- Release Date:2020/04/10 15:09
-
Measuring received energy and the transferred energy (ME96SS series).
It is possible to measure the received energy and the transferred energy separately. More Details >>
- No:22176
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:53
-
Replied value on the communication operation test of test mode (ME96SS series).
(A) Measurement values As for the measurement elements on the test mode screen, the set values are displayed. As for the other measurement elements, 0 is ... More Details >>
- No:22185
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:17
-
Display digit of ACTIVE ENERGY
In the case of "6-digit display", the upper 3 digits of "9-digit display" are hidden. For details, refer to the Instrument User's Manual which you use. ・El... More Details >>
- No:24809
- Release Date:2019/03/27 14:44