FAQ within [ Electrical Indicators ]
-
Measuring harmonics range (ME96SS series).
ME96SSHB-MB • Total harmonics and odd orders of harmonics from 1st to 31st •Effective value and distortion rate. • Harmonic current and Harmonic... More Details >>
- No:22173
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:46
-
Wiring for only measuring current (ME96SS series).
It is unnecessary. (It is necessary to prepare an auxiliary power supply which supplies power between MA and MB.) More Details >>
- No:22174
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:50
-
Measuring received energy and the transferred energy (ME96SS series).
It is possible to measure the received energy and the transferred energy separately. More Details >>
- No:22176
- Release Date:2018/08/27 16:41
- Update:2020/04/10 16:53
-
Error in the measurement value (ME96SS series).
There is a possibility of the wiring error for VT/CT to this model. Please check the wiring for VT/CT and this model. More Details >>
- No:22179
- Release Date:2018/08/27 16:41
-
Setting for communication (ME96SS series).
1) For the main body of ME96: Please set the following values on the “Set-up menu 2”. In case of MODBUS RTU Set-up menu No. Setti... More Details >>
- No:22181
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:05
-
Acquired values through MODBUS RTU.
The acquired value by communication should be multiplied by the multiplying factor to change into the measurement value. Please refer to Section 7.3 of ... More Details >>
- No:22183
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:13
-
Register address for active energy monitors in the MODBUS RTU communication (ME96SS series).
The acquired digit length of “1280”, “1281” and “1304” varies with the full load power. The acquired digit length of “1304” is 6-digit. Each of “1280” and... More Details >>
- No:22184
- Release Date:2018/08/27 16:41
- Update:2020/04/10 17:18
-
Replied value on the communication operation test of test mode (ME96SS series).
(A) Measurement values As for the measurement elements on the test mode screen, the set values are displayed. As for the other measurement elements, 0 is ... More Details >>
- No:22185
- Release Date:2018/08/27 16:41
- Update:2020/04/13 09:17
-
Concurrent-use of MODBUS RTU and CC-Link.
MODBUS RTU communication and CC-Link communication can be used at the same time. More Details >>
- No:22187
- Release Date:2018/08/27 16:41
-
Concurrent-use of MODBUS RTU and MODBUS TCP (ME96SS series).
MODBUS RTU communication and MODBUS TCP communication can be used at the same time. More Details >>
- No:22188
- Release Date:2018/08/27 16:41